Wiring Guide

34
2 EXP Zone Valve Controls Connected Together with DHW Pump
24 VAC
FACTORY
INSTALLED
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
H
N
BOILER
24 VAC
FACTORY
INSTALLED
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
24 VAC
FACTORY
INSTALLED
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
24 VAC
FACTORY
INSTALLED
TRANSFORMER
120 VAC
INPUT
WHITE
BLACK
SWITCH SETTINGS
Master/Slave: Master
Priority Zone: On
Reset/Normal: Normal
SWITCH SETTINGS
Master/Slave: Slave
Priority Zone: Off
Reset/Normal: Normal
120 VAC
INPUT
MASTER
SLAVE
DHW
PUMP
DRY
CONTACTS
TO: BOILER AQUASTAT RELAY
TO: "TT" ON BOILER WITH
DHW "TT" INPUT
1234
ZONE 1
1234
ZONE 2
1234
ZONE 3
1234
ZONE 4
1234
ZONE 5
1234
ZONE 6
PRIORITY
ZONE
2 WIRE ZONE VALVE
(NO END SWITCH)
MUST USE JUMPER
TACO
3 WIRE
ZONE VALVE
1
2
3
JUMPER
3 & 4
MOTOR END
SWITCH
4 WIRE ZONE VALVE
(POWER OPEN,
SELF CLOSING)
JUMPER
3 & 4
ZVC 406-EXP-4
SIX ZONE EXPANDABLE
ZONE VALVE CONTROL
POWER IN
24 VAC
N/O COM N/C
ZONE 6 PUMP
END SWITCH
SLAVE
PRIORITY ON
RESET
POST PURGE ON
PRIORITY PROTECTION ON
PUMP EXERCISE ON
30 SEC/2 WK
MASTER
OFF
NORMAL
OFF
OFF
OFF
4 MIN/24 HOUR
THERMOSTATS (24 VAC)
T STAT 1
VALVE 1
T STAT 2
VALVE 2
T STAT 3
VALVE 3
T STAT 4
VALVE 4
VALVE 5
T STAT 6
VALVE 6
POWER
LED
INDICATORS
T STAT 5
ZONE 1 ZONE 2
ZONE 3
ZONE 4 ZONE 5 ZONE 6 NET
EXPANSION
MAIN
PRIORITY
XX
XX
AB
CRW
CRW
CRW
CRW
CRW
CRW
C
12
END SWITCH THERMOSTATS (24 VAC)
PRIORITY
24 VAC ZONE VALVES
1234
ZONE 1
1234
ZONE 2
1234
ZONE 3
1234
ZONE 4
1234
ZONE 5
1234
ZONE 6
PRIORITY
ZONE
2 WIRE ZONE VALVE
(NO END SWITCH)
MUST USE JUMPER
TACO
3 WIRE
ZONE VALVE
1
2
3
JUMPER
3 & 4
MOTOR END
SWITCH
4 WIRE ZONE VALVE
(POWER OPEN,
SELF CLOSING)
JUMPER
3 & 4
ZVC 406-EXP-4
SIX ZONE EXPANDABLE
ZONE VALVE CONTROL
POWER IN
24 VAC
N/O COM N/C
PUMP END
SWITCH
ZONE 6 PUMP
END SWITCH
SLAVE
PRIORITY ON
RESET
POST PURGE ON
PRIORITY PROTECTION ON
PUMP EXERCISE ON
30 SEC/2 WK
MASTER
OFF
NORMAL
OFF
OFF
OFF
4 MIN/24 HOUR
THERMOSTATS (24 VAC)
INDIRECT
WATER HEATER
AQUASTAT OR
THERMOSTAT
T STAT 1
VALVE 1
T STAT 2
VALVE 2
T STAT 3
VALVE 3
T STAT 4
VALVE 4
VALVE 5
T STAT 6
VALVE 6
POWER
LED
INDICATORS
T STAT 5
ZONE 1 ZONE 2
ZONE 3
ZONE 4 ZONE 5 ZONE 6 NET
EXPANSION
MAIN
PRIORITY
XX
XX
AB
CRW
CRW
CRW
CRW
CRW
CRW
C
12
END SWITCH THERMOSTATS (24 VAC) PRIORITY
24 VAC ZONE VALVES
PRIORITY
PRIORITY
XX
PUMP END
SWITCH
XX
POWER
CONTROLS
ACCESSORY
PORT
FUSE
5 AMP
FUSE
5 AMP
POWER
CONTROLS
ACCESSORY
PORT
FUSE
5 AMP
FUSE
5 AMP
NOTE 2: When a circulator
is used on the priority zone
instead of a zone valve,
jumper 3 and 4 of the
priority zone.
See NOTE 2
NOTE 1: Terminals C are for
optional 24V thermostat
COMMON connections.
Powered from Transformer A
A
B
A
B
Powered from Transformer A
Powered from Transformer B
Powered from Transformer A
Powered from Transformer B
Powered from Transformer B
See NOTE 1
TTT
TTT
BOILER TURNS ON WHEN
ANY ZONE VALVE OPENS.
DHW PUMP TURNS ON ONLY
WHEN PRIORITY ZONE CALLS.