Wiring Guide

95
Instruction Sheet
SR501-OR-4 Switching Relay with Outdoor Reset
ONE ZONE INSTALLATION W/O INDIRECT DHW
ONE ZONE
SWITCHING RELAY
WITH OUTDOOR RESET
SR 501OR-4
LED
INDICATORS
POWER
TSTAT
DHW
OVERRIDE
BOILER
RELAY
NH
INPUT
120 VAC
ZONE 1
120 VAC
NH
6
AMP
X
R
BOILER TSTAT
W
CR
W
DHW
OUTDOOR
SENSOR
SUPPLY
SENSOR
X
DESIGN OUTDOOR
TEMPERATURE
FOR 180°F SUPPLY
TEMPERATURE
OFF
-30
-20
0
-10 10
20
40
30
ON
SW1
OFF
SYSTEM
CIRCULATOR
(OPTIONAL)
N
H
POWER
INPUT
(120 VAC)
24 VAC
THERMOSTAT
BOILER
CONTROL
OUTDOOR
SENSOR
BOILER
SUPPLY
SENSOR
POT1
MULTI-ZONE INSTALLATION WITH ZONE CONTROL, WITH INDIRECT DHW
ONE ZONE
SWITCHING RELAY
WITH OUTDOOR RESET
SR 501OR-4
LED
INDICATORS
POWER
TSTAT
DHW
OVERRIDE
BOILER
RELAY
NH
INPUT
120 VAC
ZONE 1
120 VAC
NH
6
AMP
X
R
BOILER TSTAT
W
CR
W
DHW
OUTDOOR
SENSOR
SUPPLY
SENSOR
X
DESIGN OUTDOOR
TEMPERATURE
FOR 180°F SUPPLY
TEMPERATURE
OFF
-30
-20
0
-10 10
20
40
30
ON
SW1
OFF
SYSTEM
CIRCULATOR
(OPTIONAL)
N
H
POWER
INPUT
(120 VAC)
BOILER
CONTROL
OUTDOOR
SENSOR
BOILER
SUPPLY
SENSOR
POT1
1234
ZONE 1
1234
ZONE 2
1234
ZONE 3
EXISTING
ZONE VALVE CONTROL
POWER IN
24 VAC
N/O
COM
N/C
PUMP END
SWITCH
FUSE
5 AMP
ZONE 3 PUMP
END SWITCH
THERMOSTATS
(24VAC)
T STAT 1
VALVE 1
T STAT 2
VALVE 2
T STAT 3
VALVE 3
POWER
LED
INDICATORS
ZONE 1 ZONE 2 ZONE 3
ISOLATED
XX
RW
RW RW
END SWITCH THERMOSTATS
PRIORITY
24 VAC ZONE VALVES PRIORITY
XX
ZONE 3
PRIORITY
OFF
ON
CCC
2 WIRE ZONE VALVE
(NO END SWITCH)
MUST USE JUMPER
TACO 3 WIRE
ZONE VALVE
1
2
3
JUMPER
3 & 4
TACO 3 WIRE
ZONE VALVE
1
2
3
DHW
AQUASTAT
A
CONTROL STRATEGY:
Outdoor Reset:
In order to properly control a hot water heating system, the heat sup-
plied to the building must equal the heat lost by the building.
The heat supplied to a building is proportional to the temperature of
the supply water and the surface area of the heating element. A
small surface area such as baseboard radiators requires a higher
water temperature than a larger surface area such as radiant floors.
The heat lost from a building is dependent on the outdoor tem-
perature, as well as other factors. As the outdoor temperature
drops, the building heat loss increases.
Reset Ratio:
Operation of a hot water heating system can generally be improved by
modulating the supply water temperature as the outdoor temperature
changes. Using this approach, the heat lost from the building is
matched by the heat input to the building. The SR501-OR boiler reset
control utilizes a reset ratio to set the relationship between outdoor
temperature and supply water temperature. The reset ratio determines
the amount the supply water temperature is raised for every 1° drop in
outdoor air temperature, and it is determined from the starting point
and the system design conditions. In order for the control to automat-
ically determine the reset ratio, outdoor design conditions must be
established. This is usually the typical coldest outdoor temperature
or it can be set by using ASHARE standards for Design Outdoor
Temperature for specific geographic locations.
APPLICATION:
The SR501-OR is a microprocessor-based control designed to regulate
the supply water temperature of a single boiler, based on the outdoor
temperature. The SR501-OR is a boiler reset control and switching relay
in one unit. The SR501-OR is ideal for retrofit application, but may also
be used in new installations as well.
The SR501-OR includes functions such as automatic reset ratio calcu-
lation, warm weather shut down (WWSD), minimum boiler temperature
setting, and boiler differential setting. The control also has boiler sensor
and outdoor sensor error checking.
40
30
20
10
0
-10
-20
-30
70
-20
90
130
110
150
170
180
190
210
90 80 70 60 50 40 30 20 10 0 -10
OUTDOOR TEMPERATURE (°F)
BOILER SUPPLY TEMPERATURE vs. OUTDOOR TEMPERATURE (°F)
FOR OUTDOOR DESIGN TEMPERATURES
BOILER SUPPLY TEMPERATURE (°F)