Install Instructions

6
Testing the Sensors
A good quality test meter capable of measuring up to 5,000 kΩ (1 kΩ = 1000 Ω) is required to measure the sensor resistance. In addi-
tion to this, the actual temperature must be measured with a good quality digital thermometer.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the iSeries-S. The wires from
the sensor must not be connected to the iSeries-S while this test is performed. The wiring terminals are easily removed by pulling them
from the iSeries-S. Using the chart below, estimate the temperature measured by the sensor. The sensor and thermometer readings
should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective
sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective.
To test for a defective sensor, measure the resistance directly at the sensor location.
Temperature
Resistance Temperature Resistance Temperature Resistance Temperature Resistance
°F °C
Ω °F °C Ω °F °C Ω °F °C Ω
-30 -34
234,196 30 -1 34,558 90 32 7,334 150 66 2,045
-20 -29 165,180 40 4 26,099 100 38 5,828 160 71 1,689
-10 -23 118,018 50 10 19,900 110 43 4,665 170 77 1,403
0 -18 85,362 60 16 15,311 120 49 3,760 180 82 1,172
10 -12 62,465 70 21 11,883 130 54 3,050 190 88 983
20 -7 46,218 80 27 9,299 140 60 2,490 200 93 829
Product Specifications
Maximum Operating Pressure: 300 PSI (2,100 kPa)
Maximum Shutoff Pressure: 125 PSI (875 kPa)
Fluid Temperature Range: 20º to 240ºF, (-7º to 115ºC) @ 135ºF (57ºC) ambient
Service: Closed systems
Water based, up to 50% Glycol
Seat Leakage: Drop-Tight Close-Off, 0-125 psi (0-862 kPa) 2 & 3-way
Electrical Rating: 24 VAC ±10%, 60 Hz
Do not exceed number of valves per transformer rating.
Example: Do not use more than 4 iSeries Mixing Valves per
40VA transformer.
Power Consumption: 7.2 Watts, 0.4 Amps
Flow Coefficients
Materials of Construction, Actuator
Body: High Performance Engineered Polymer
Gears: High Performance Internally Lubricated Engineered Polymer
Materials of Construction, Valve
Body: Forged Bronze
Stem: Brass
Press Ring: Brass
Ball: Brass (Chrome Plated)
Seat (2, 3-way): Modified Teflon
O-rings: EPDM
* At 4' per second (maximum recommended residential flow rate).
Valve
Size
2-way CV (KV)/FT.
of Pipe Equiv.*
3-way CV (KV)/FT.
of Pipe Equiv.*
4-way CV (KV)/FT.
of Pipe Equiv.*
Sweat & Threaded Union
1
2
"
4.9 (4.3) / 9.5 1.5 (3.0) / 18.6 3.5 (3.0) / 18.6
3
4
"
10.3 (8.9) / 8.4 3.5 (3.0) / 73.0 4.5 (3.9) / 44.2 7.0 (6.1) / 19
1" 8.9 (7.7) / 47.4 4.0 (3.5) / 234.9 4.5 (3.9) / 185.6 9.3 (8.1) / 44
1
1
4
"
17.5 (15.2) / 26