Install Instructions

Listings/Approvals:
UL Guide (NKPZ) for industrial control
equipment per UL Standard 508 Indus-
trial Control Equipment
UL Guide (MFHX) for heating/cooling
appliance switch per UL Standard 353
Limit Controls
CSA Class (321106) for industrial con-
trol equipment per CSA Standard C22.2
No. 14-M Industrial Control Equipment
CE Marked
Maximum Service Pressure: 250 PSI
Enclosure: Die-cast housing and high impact
resistant polycarbonate cover.
Not for use in hazardous loca-
tions.
Contacts:
One SPDT (Form C) switch
10 Amps at 125/250VAC
.5 Amps at 125VDC
.25 Amps at 250VDC
Motor Ratings : 115VAC 230VAC
Horsepower : 1/3 1/3
AC F.L.A. : 7.2 3.6
AC L.R.A. : 43.2 21.6
Pilot Duty Rating : 332VA 120/240VAC
Environmental Specifications:
Suitable for indoor or outdoor use with
factory installed gasket and die-cast hous-
ing.
NEMA 4 Rated Enclosure - use with appro-
priate conduit fitting.
Ambient Temperature Range:
32°F to 151°F (0°C to 66°C)
Media Temperature Range:
-20°F to 250°F (-29°C to 121°C)
Pipe Connection:
IFSWSB: 1 in. NPT Brass
IFSWSS: 1 in. NPT 316 Stainless Steel
Conduit Entrance: One opening for 1/2"
conduit
Usage: For pipe sizes 1" - 8"
Caution: This device is not intended for appli-
cations in explosive environments.
GENERAL
The IFSWS Series is a low turn radius (1.88")
flow switch used in liquid flow lines carrying
water or any fluid not harmful to brass, stain-
less steel, EPDM or fluorosilicone, and not
classified as a hazardous fluid.
This switch can serve as a way to start and
stop electrically operated equipment when a
flow or no flow condition occurs in a variety of
applications.
This device is designed for use only as an
operating control. Where an operating control
failure would result in personal injury and/or
loss of property, it is the responsibility of the
installer to add devices (safety, limit controls)
that protect against, or systems (alarm, super-
visory systems) that warn of control failure.
# 5401117-REV E
EFFECTIVE: March 17, 2004
102-026
Instruction Sheet
IFSWS Industrial Flow Switch
SUPERCEDES: 102-026 DATED January 1, 2002

Summary of content (4 pages)