Install Instructions

Multi-Function LED and Troubleshooting:
This troubleshooting table is intended as a helpful guide and is not all inclusive. There could be other causes and solutions for a
non-functioning product.
4 7/8
2 1/8
3 1/2
4 3/8
7/8
3 1/8
1 9/16
LED STATUS
POWER
LED STATUS
BATTERY ONLY
INDICATES POSSIBLE CAUSE POSSIBLE SOLUTION Audible Alarm
S
olid Green
-
----------
N
ormal
----------- 1 Green Blink
e
very 10 Seconds
(
Approximately)
Normal ----------- ----------- -----------
Solid Green with
o
ne red blink
----------- Low Batteries Low Batteries Replace batteries Chirp every 60 second
B
atteries installed incorrectly
I
nstall batteries correctly
C
hirp every 60 second
N
ot illuminated
-
----------
P
ower off
P
ower supply not plugged in
P
lug in power supply
-
----------
-
-----------
N
ot illuminated
P
ower off
B
atteries installed incorrectly
o
r not at all
I
nstall batteries correctly/
i
nstall batteries
-
----------
I
n between cycles
N
ormal
W
ait 15 seconds for indication
blinks
Solid Red with 2
red blinks
Solid dim Red with
2 red blinks
S
ensor error
B
ad wire connection
Make sure wiring connections
a
re solid and tight and the
quick connect is all the way in
Chirp every 60
s
econds
Make sure sensors wired per
i
nstructions
Chirp every 60
s
econds
Solid Red with 3
r
ed blinks
Solid Dim Red with
3
red blinks
Valve error Valve is not connected to the
c
ontrol
Connect the valve to the con-
t
rol
Chirp every 60
s
econds
B
ad wire connection
M
ake sure wiring connections
are solid and tight and the
q
uick connect is all the way in
C
hirp every 60
seconds
Solid Red with 3
red blinks
----------- AC power error Wrong power supply Use power supply provided Chirp every 60
seconds
Continuous Red
blinks
Continuous Red
blinks
LeakBreaker has
Triggered
Sensor has detected water Determine the water source
and correct. Dry the sensor
and reset the LeakBreaker.
Press the open button to reset.
Constant alarm.
Press the mute button
to silence the alarm.
Solid Red Solid Red LeakBreaker has trig-
gered and the water on
the sensor has dried up
Sensor has detected water Determine the water source
and correct. Press the open to
reset.
Constant alarm.
Press the mute button
to silence the alarm.
Dimensions (for reference purposes):