Specification

101-096
Model 00R-IFC
®
Radiant Heating Circulator
Effective: July 1, 2009 Supersedes: April 1, 2006
Submittal Data Information
Job: Engineer:
Contractor:
Rep:
ITEM NO. MODEL NO. IMP. DIA. G.P.M. HEAD/FT. H.P. ELEC. CHAR.
Do it Once. Do it Right.
®
TACO INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 Fax: 942-2360
TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3 Telephone: (905) 564-9422 Fax: (905) 564-9436
Visit our website at: www.taco-hvac.com
Printed in USA
Copyright 2009
TACO, Inc.
Submittal Data Information
Model 00R-IFC
®
Radiant Heating Circulator
Submittal Data # 101-096
Supersedes: 4/1/06
Effective: 07/01/09
Performance Field - 60Hz
Pump Dimensions & Weights
Mounting Positions
Standard Optional
OK if over 20 psi
Flange Orientation
Features
s
Specifically designed for radiant heating applications
s)NTEGRAL&LOW#HECK)&#
®
)
Simplifies piping
Prevents gravity flow / reverse flow
Eliminates separate in-line flow check
Reduces installed cost
Improves performance
Easy to service
s,%$INDICATORLIGHT
s5NIQUEREPLACEABLECARTRIDGEFIELDSERVICEABLE
s5NMATCHEDRELIABILITYMAINTENANCEFREE
s1UIETEFFICIENTOPERATION
s3ELFLUBRICATINGNOMECHANICALSEAL
s
Cast iron or stainless steel construction, flanged
connections
Materials of Construction
Casing (Volute): Cast Iron or Stainless Steel
Integral Flow Check (IFC
®
):
Body, Plunger....Acetal
O-ring Seals......EPDM
Spring.................Stainless Steel
Stator Housing: Steel
Cartridge: Stainless Steel
Impeller: Non-Metallic
Shaft: Ceramic
Bearings: Carbon
O-Ring & Gaskets: EPDM
Model Nomenclature
F – Cast Iron, Flanged
SF – Stainless Steel, Flanged
IFC – Integral Flow Check
Performance Data
Flow Range: 0 - 12.5 GPM
Head Range: 0 - 15 Feet
Minimum Fluid Temperature: 40˚F (4˚C)
Maximum Fluid Temperature: 230°F (110˚C)
Maximum Working Pressure: 125 psi
Connection Sizes: 3/4”, 1”, 1-1/4”, 1-1/2” Flanged
FOR INDOOR USE ONLY
Model Volts Hz Ph Amps RPM HP
Cast Iron
115 60 1 .79 3250 1/25
Stainless Steel 115 60 1 .84 3250 1/25
Motor Permanent Split Capacitor
Type Impedance Protected
Electrical Data
Application
The 00R-IFC Radiant Heating circulator with Integral Flow Check specifically fits the higher head and
lower flow designs used in many Radiant Heating systems. The circulator's performance curve deliv-
ers flow that can be used in a wide combination of tube diameters and length of runs. The removable,
spring loaded Integral Flow Check (IFC) prevents gravity flow/reverse flow. By locating the IFC inside
the pump casing, a separate in-line flow check is eliminated, simplifying piping and reducing installation
costs. It also makes for a modern, clean looking job when mounting the pump in vertical runs of pipe,
pumping away from the boiler. Both the IFC and cartridge are easily accessed for service instead of
replacing the entire unit. Available in Cast Iron and Stainless Steel construction.
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com
A B C D E F Ship Wt.
Model Casing in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
00R-F6-1 IFC
Cast Iron 5-15/16 151 4-1/2 114 3-3/16 81 2-15/16 75 5 127 6-3/8 162 9 4.0
00R-SF6-1 IFC 5-15/16 151 4-1/2 114 3-3/16 81 2-15/16 75 5 127 6-3/8 162 8 3.6
00R-SF6 IFC 6 152 4 102 3-3/16 81 2-15/16 75 5 127 6-3/8 162 8 3.6
Stainless
Steel
00R-SF6-IFC only
FOR INDOOR USE ONLY