Submittal Sheet
101-182
Multi-Volt Zone Sentry
®
Effective: May 30, 2016 Supersedes: New
Submittal Data Information
Job: Engineer:
Contractor:
Rep:
ITEM NO. MODEL NO.
A Taco Family Company
2016
Valve
Size
2-Way
Cv (Kv) / Ft of
Pipe Equiv. *
Close-Off
Pressure
(kPa)
3-Way
Cv (Kv) / Ft of
Pipe Equiv. *
1/2” 4.9 (4.3) / 9.5 0-125 psi (0-862 kPa) 1.5 (1.3) / 111
3/4” 10.3 (8.9) / 8.4 0-125 psi (0-862 kPa) 3.3 (2.8) / 82
1” 8.9 (7.7) / 47.4 0-125 psi (0-862 kPa) 3.0 (2.6) / 411
Multi-Volt Zone Sentry®
Product Specifications
Max. Operating Pressure ............................300 PSI (2100 kPa)
Max. Shutoff Pressure ...................................125 PSI (875 kPa)
Max. Ambient Temp. ....................................135˚F
Fluid Temp. Range .........................................20-220˚F (-7˚-104˚C)
Service ...................................................................Closed systems
....................................................................................Optional open system
....................................................................................configuration available
....................................................................................Water/Water and glycol
....................................................................................up to 50%
Seat Leakage .....................................................Drop-Tight Close-Off
Electrical Rating ...............................................120 VAC to 277VAC, 1Ph, 50/60Hz
Power Consumption ....................................4 Watts
Power Consumption ....................................1.5 Watts
Max. Duty Cycle ...............................................1 Cycle/Minute
Materials of Construction, Actuator:
Body ........................................................................High Performance
....................................................................................Engineered Polymer
Gears .......................................................................High Performance Internally
....................................................................................Lubricated Engineered Polymer
Materials of Construction, Valve:
Body ........................................................................Forged Brass
Stem ........................................................................Brass
Press Ring ............................................................Brass
Ball ............................................................................Brass (Chrome Plated)
Seat ..........................................................................Modified Teflon®
O-Rings .................................................................EPDM
(Charging)
(Power On)
Multi-Volt Zone Sentry® Dimensions: FOR REFERENCE PURPOSES
Valve Size
A B C D
E
(Sweat)
E
(Threaded)
F G
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
1/2” 2-5/8” 66.6 2-3/8” 60.3 4-7/8” 123.8 3-3/4” 95.3 3-1/8” 79.4 3-3/4” 95.3 1-9/16” 39.7 2-5/16” 58.7
3/4” 2-5/8” 66.6 2-3/8” 60.3 5” 127 3-7/8” 98.4 3-1/8” 79.4 3-5/16” 84.1 1-9/16” 39.7 2-5/16” 58.7
1” 2-5/8” 66.6 2-3/8” 60.3 5” 127 3-7/8” 98.4 3-7/8” 98.4 3-7/8” 98.4 1-7/8” 47.6 2-5/16” 58.7
*At 4’ per second (Max. recommended residential ow rate).
NPT Models
Normally Closed
2-Way
Sweat Models
Normally Closed
V050T2A2ZALNVE2A1 1/2" 2-way V050C2A2ZALNVE2A1
V075T2A2ZALNVE2A1 3/4" 2 way V075C2A2ZALNVE2A1
V100T2A2ZALNVE2A1 1" 2-way V100C2A2ZALNVE2A1
NPT Models 3-Way
Sweat
Models
V050T3A1ZALNVE2A1 1/2" 3-way V050C3A1ZALNVE2A1
V075T3A1ZALNVE2A1 3/4" 3-way V075C3A1ZALNVE2A1
V100T3A1ZALNVE2A1 1" 3-way V100C3A1ZALNVE2A1
Consult factory for additional model numbers.
Application:
One valve takes the place of many. The Multi-Volt Zone Sentry will accept input
voltages between 120 and 277VAC 50/60HZ. The Multi-Volt Zone Sentry zone valve
is designed for use in hydronic HVAC systems, primarily in fan coils and air handlers
or other HVAC systems where a quality line voltage zone valve is required. The Zone
Sentry can be installed in both heating and cooling applications and is available in
a normally closed or normally open configuration.
Submittal Data#101-182 • Eective: 05/30/16 • Supersedes: New
Zone Sentry® Series