Install Instructions

4
VIRIDIAN STATES
INPUT SETTING INPUT CONNECTIONS
PUMP
STATE
RELAY
SETTING
(Default = Error)
RELAY
STATUS
(Normally Open)
IO1 IO2
IO1
Closed: <2 Vdc
IO2
Closed: >8 Vdc
NF (0) NF (0)
OPEN OPEN RUN
RUN
CLOSED
OPEN CLOSED RUN
RUN
CLOSED
CLOSED OPEN RUN
RUN
CLOSED
CLOSED CLOSED RUN
RUN
CLOSED
RUN NF (0)
OPEN OPEN RUN
RUN
CLOSED
OPEN CLOSED RUN
RUN
CLOSED
CLOSED OPEN OFF RUN OPEN
CLOSED CLOSED OFF RUN OPEN
NF (0) RUN
OPEN OPEN OFF RUN OPEN
OPEN CLOSED RUN
RUN
CLOSED
CLOSED OPEN OFF RUN OPEN
CLOSED CLOSED RUN
RUN
CLOSED
RUN RUN
OPEN OPEN OFF RUN OPEN
OPEN CLOSED RUN
RUN
CLOSED
CLOSED OPEN OFF
RUN
CLOSED
CLOSED CLOSED OFF
RUN OPEN
MAX NF (0)
OPEN OPEN MAX
RUN
CLOSED
OPEN CLOSED MAX
RUN
CLOSED
CLOSED OPEN RUN
RUN
CLOSED
CLOSED CLOSED RUN
RUN
CLOSED
NF (0) MAX
OPEN OPEN RUN
RUN
CLOSED
OPEN CLOSED MAX
RUN
CLOSED
CLOSED OPEN RUN
RUN
CLOSED
CLOSED CLOSED MAX
RUN
CLOSED
RUN
(Default)
MAX
(Default)
OPEN OPEN RUN
RUN
CLOSED
OPEN CLOSED MAX
RUN
CLOSED
CLOSED OPEN OFF RUN OPEN
CLOSED CLOSED OFF RUN OPEN
MAX RUN
OPEN OPEN OFF RUN OPEN
OPEN CLOSED MAX
RUN
CLOSED
CLOSED CLOSED RUN
RUN
CLOSED
CLOSED OPEN OFF
RUN OPEN
MAX MAX
OPEN OPEN MAX
RUN
CLOSED
OPEN CLOSED MAX
RUN
CLOSED
CLOSED OPEN RUN
RUN
CLOSED
CLOSED CLOSED MAX
RUN
CLOSED
LEGEND: NF = “No Function” Setting BOLD = Pump Running BOLD ITALIC = Maximum Speed
NOTE : IO1 “CLOSED” means connected to 0 - 2 Vdc
IO2 “CLOSED” means connected to 8 - 24 Vdc