Install Instructions
5
5.3 Constant Duty Curve (Unregulated Pump) Control:
An unregulated pump
decreases its head with
increasing flow. This unreg-
ulated setting can be
achieved by setting the
limit head (Hmax) to “no
limit (99)” in the pump tab
(see below) with a jumper
across IO2/24V (or 8Vdc
and above). Note: I1 must
be closed and set to "no
function". Limit rpm to
should be set to the maxi-
mum value to achieve full
pump curve. This allows the pump to run just like a conventional
non-variable speed pump.
5.4 RPM Regulation:
Provides regulation similar
to a manually adjustable
pump.
5.5 Power Limitation:
Artificially limits power
consumption and output
by selecting a maximum
amp draw.
6. CONNECTION TO A NETWORK - PUMP SETUP:
In order to change the factory default operating parameters of the
pump or to use various web tools the pump needs to be con-
nected to a network or a personal computer over the Ethernet
plug. Use CAT-4 or better network cable connected to “PATCH”
configuration if plugged into a network or connect an Ethernet
cable directly between a PC and the Viridian.
To achieve pump IP protection, network cable should be fed
through the glanded inlet and then crimped to a connector.
Ethernet plug is galvanically insulated, but the rest of the cabling
could still present shock hazard.
If more than one pump will be connected into network, each indi-
vidual pump should have its IP address and NetBIOS name
changed and noted. That will prevent network confusion and pro-
vide naming service in relation to pump function.
6.1 Web Interface Settings:
When the Viridian is connected to a network or another computer,
it can be reached by typing its IP address or NetBIOS name into
the internet explorer’s address line. The default IP address is
192.168.0.245 and default NetBIOS name is “viridian”. The pump
can be switched between standby mode or maximum power via
the digital inputs.
6.2 Setting Up the Default IP Address:
Once the Ethernet cable is connected between the Viridian pump
and either the laptop or network, go to your Control Panel and
select Network Connections. Right click on Local Area
Connection and choose properties. Highlight Internet Protocol
Version 4 (TCP/IPv4) then click on properties. In the TCP/IP
address use the following IP address “192.168.0.XXX” (example
192.168.0.123). Click OK to finish.
CAUTION: All connections should be made with
the power to the pump turned off.
ATTENTION: Tous les raccordements doivent être
effectués avec l'alimentation électrique vers la
pompe coupée.
INTERNET
ROUTER ROUTER
LAPTOP
PC
LAPTOP
CONNECTING VIRIDIAN with ETHERNET CABLE
CONNECTING VIRIDIAN on LAN
ETHERNET CABLE CONNECTED TO VIRIDIAN
H
Q
CONSTANT
DUTY
CONTROL
Max RPM or
Unregulated Curve
R
educed RPM
C
urves
H
Q
POWER
LIMITATION
CONTROL
Max Power
Curve
R
educed Power
(
watt) Curves