Install Instructions

6
6.3 Connecting to the Pump:
Go to Internet Explorer, in the address line type http://viridian or
the IP address of the pump.
6.4 Overview Page:
The overview page allows you to view the current status of the
pump. You may select the intervals (never, every 30 seconds,
every 3 seconds) of which you would like the data refreshed. It
displays pump operation summary information, including:
• Power Consumption Heatsink Temperature
• Amperage • Operating Hours
• RPM • Number of Restarts
• Estimated Head • Accumulated Power
• Estimated Flow Consumption
• Estimated Efficiency • Digital Inputs
• Motor Status • Relay Status
6.5 Pump Settings:
For more detail or to change any of the pump settings click on the
Pump tab.
Limit head (Hmax) will set the maximum allowable head.
Hmax proportional to Q will set the ratio between head
and flow:
Hmax = 0%: Constant pressure is set and should not exhib-
it noticeable change until maximum power is reached.
Hmax = X%: Parameter will set the percentage of drop
in head from maximum to closed valve.
Limit rpm to will limit motor speed.
Limit power to will set maximum wattage (max power
consumption of the pump).
Limit grid current to will assign a maximum amp draw.
Limit heatsink temperature to will set a maximum
temperature at the heatsink (electronics area).
Switch on the relay when can be set up as:
Standby (operation)
Active (run)
Error detected (error)
Active I2 (i2)
Input I1 is either:
Run
Run the pump (run)
Full power (max)
No function (0)
Input I2 has the functions the same as I1.
SAVE will write
settings in permanent non-volitile memory.