Install Instructions
10.2 LAN (Local Area Network) Setting:
The factory default IP Address of the Viridian is 192.168.0.245. It
i
s not necessary to change this unless multiple Viridians are con-
nected to the same router. See Notes below.
Set Router LAN TCP/IP as follows:
• IP Address 192.168.0.1
• IP Subnet mask 255.255.255.0
Set Router DHCP as follows:
• Check “Use Router as DHCP Server” box
• Starting IP Address 192.168.0.2
• Ending IP Address 192.168.0.100
10.3 Steps to Communicate with the Viridian After Changes
are Complete:
Plug in an Ethernet cable to the device input at the back of the
router (not the Internet or “WAN” input) and to the Ethernet con-
nection at the Viridian.
Power up all devices (the Viridian can be forced into standby by
placing a jumper across I01 and 0V digital input to eliminate dry
operation of the rotating assembly).
Connect to the wireless network with the iPhone (or other wireless
device), using the network name set in the “Wireless Setting” section.
Open up the device web software (Safari, Windows Explorer,
Firefox etc.).
Open the website “Viridian” or enter the pump’s IP Address
192.168.0.245 in the address window, click enter.
Connection is complete and status or adjustments to the Viridian
can be made.
Notes:
Multiple Viridians can be plugged into the router, although each
pump would require a different IP address and name.
No other changes to the router are required from factory settings.
11. SPECIFICATIONS AND PUMP CHARACTERISTICS:
11.1 Application:
• Maximum Operating Pressure: 175 PSI (12 bar)
• Water Temperature Range: 14º – 230ºF (-10º – 110ºC)
• Ambient Operation Temperature Range: 32º – 104ºF
(0º – 40ºC). Ambient temperature should be 104ºF (40ºC)
or lower when fluid temperature exceeds 194ºF (90ºC).
• Minimum static inlet pressure at pump suction port
(PSI / bar) to avoid cavitation at fluid temperatures:
• Designed for closed loop heating and cooling systems
pumping water or a water/glycol mixture.
• For indoor use only - employer uniquement a l’interieur.
11.2 Electrical Data:
• Pump Ratings: 1 phase, 110 - 240V, 47 - 63Hz (VR15 & VR20)
1 phase, 200 - 240V, 47 - 63Hz (VR25 & VR30)
• Power Consumption (HP): VR15 = 0.027 - 0.680 HP
V
R20 = 0.035 - 1.088 HP
VR25 = 0.054 - 1.496 HP
VR30 = 0.054 - 2.175 HP
• Power Consumption (W): VR15 = 20 - 500 W
VR20 = 26 - 800 W
VR25 = 46 - 1100 W
VR30 = 40 - 1600 W
• Rated Current (1 phase, 115/230V): VR15 = 2.2 A - 6.0 A
V
R20 = 3.5 A - 6.0 A
• Rated Current (1 phase, 230V): VR25 = 8.0 A
VR30 = 8.0 A
• 24V Supply Output: Max. Current up to 100 mA,
Output Voltage of 24V ± 20%,
Output Ripple under 1V
• Relay Output: 8A, Max. Voltage 250 VAC, 48 VDC
Max. Load up to 500 VA
• Digital Inputs: Max. Input Voltage = 32VDC
Input Impedance ~5kΩ
Logical »1« Voltage > 8V
Logical »0« Voltage < 2V
Insulation to Supply Voltage = 4kV @ 1s,
275V permanent
• Continuous Duty
• Built-in Startup Circuit
11.3 Standards, Protection and Connection:
• Insulation: Class H
• Enclosure: Class 2, IP44
• Integrated Motor Protection (electronically protected)
• UL 778, 1004-1, 508C
• CAN/CSA C22.2 #108, #100, #107.1
• EMC (89/366 EEC): EN 61000
• LVD (73/23/EC): EN 60335-1, EN 60335-2-51
• Machine Safety (98/37/EC): EN ISO 12100
• Flange Connections: ANSI 4-bolt
11.4 Ethernet Specifications:
• Connector: RJ-45 Ethernet Cable
• Speed: BASE-10, 10 Mbit/s
• Galvanic Insulation to Digital Inputs: 1.5kV @ 1s,
48V permanent
• Galvanic Insulation to Line Voltage: 4kV @ 1s,
275V permanent
• Connections: TCP/IP
• Services: http server and client, FTP server
• Web Language: HTML 1.1
11.5 Materials of Construction:
• Casing: Cast Iron
• Impeller: Stainless Steel
• Shaft: Stainless Steel
• Bearing: Metal Impregnated Carbon
11.6 Operating Modes:
• Constant Pressure Control (∆p-c)
• Variable Differential Pressure Control (∆p-v) - factory default
• Proportional Pressure Control
• Constant Curve Duty (uncontrolled pump)
• RPM Regulation
• Power Limitation
11.7 Additional Operating Modes for Two Pumps in Parallel:
• Alternating Operation (every 24 hours)
• Standby Operation
11.8 Communication:
• Web Interface (data exchange)
• XML Control Transfer Protocol
• External Digital Input/Output: 2 Inputs & 1 Output
9
FLUID
TEMPERATURES
VR15 & VR20
(PSI / bar)
VR25 & VR30
(PSI / bar)
112ºF (50ºC) 7.3 / 0.5 4.35 / 0.3
176ºF (80ºC) 11.6 / 0.8 14.5 / 1.0
230ºF (110ºC)
20.3 / 1.4 23.2 / 1.6