Specifications
Maximum Shut-off Head: 22 feet
Maximum Flow: 18 gpm
Maximum Operating Pressure: 125 psi
(862 kPa)
Maximum Water Temp: 230°F (110°C)
Minimum Water Temp: 36°F (2°C)
Electrical specifications:
Voltage: 110-120V, 50/60 Hz,
Single phase
Operating Power Range: 9W to 58W
Maximum AMP Rating: 0.67
Equipped with a cast iron casing
and should be used for closed
loop systems only.
Taco circulator pumps are
for indoor use only
Acceptable for use with water or
maximum of 50% water/glycol solution.
Model
Flange
Code
A B C D F G Ship Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
VT2218F S 8-1/8 207 6 153 3-1/4 82 2 54 4-1/4 107 6-3/8 161 7-3/4 3.52
VT2218F/4 U 8-1/8 207 6 153 3-1/4 82 2 54 4-1/4 107 6-3/8 161 7-3/4 3.52
Pump Dimensions & Weights
Electrical Data
Model Volts Hz Ph Max.Amps RPM
All Models
110/120 50/60 1 .67 1650 - 4200
Motor
Type
ECM, Permanent Magnet, Electronically Protected
Speed 1 Speed 2 Speed 3 Speed 4
9 24 40 58
Materials of Construction:
Casing: ...............................Cast Iron
Stator Housing: .............Aluminum/Composite
Cartridge: ..........................Stainless Steel
Impeller: ............................Non-Metallic
Shaft: ....................................Ceramic
Bearings: ............................Ceramic
O-Ring & Gaskets: ........EPDM
Integral Flow Check (IFC
®
):
Body, Plunger .......Acetal
O-ring Seal .............EPDM
Spring ........................Stainless Steel
A
B
C
G
D
F
Applications
The VT2218 is a temperature sensing, variable speed, high-efficiency wet
rotor circulator with an ECM permanent magnet motor. Its ideal for Delta-T
or setpoint temperature applications. Typical uses include hydronic sys-
tems zoned with zone valves, radiant loops, injection pumping, snowmelt
or hydro-air fan coils. Can also be used in constant speed mode for zoning
with circulators, indirect water heaters or primary boiler loops.
Maximum Watts
Mounting Positions Flange Orientation
Standard (S) Universal (U)
Submittal Data # 101-169 Eective: 09/16/15