Install Instructions

Product Specifications:
Maximum Operating Pressure: 300 PSI (2,100 kPa)
Maximum Shutoff Pressure: 125 PSI (875 kPa)
Maximum Ambient Temperature 135°F
Fluid Temperature Range: 20° to 220°F, (-7° to 105°C)
Service: Closed systems
Optional open system configuration available
Up to 50% Glycol
Ball Rotation Speed: Full Open to Full Close (90° turn), 5 seconds (after charge time)
Full Close to Full Open (90° turn), 5 seconds (after charge time)
Seat Leakage: Drop-Tight Close-Off
Electrical Rating: 24 VAC, 60 HZ, 0.48 Amps
Do not use more than 12 zone valves per 40VA transformer.
Power Consumption, Charging: 11.4 Watts, 0.48 Amps
Power Consumption, Power On: 1.44 Watts, 0.06 Amps
Heat Anticipator Setting: 0.5 Amps
End Switch Rating: 1 Amp @ 24 VAC
NOTE: Some power robbing thermostats may cause a reduction of the number of valves possible per 40VA transformer.
Materials of Construction, Actuator:
Body: High Performance Engineered Polymer
Gears: High Performance Internally Lubricated Engineered Polymer
Materials of Construction, Standard Valve:
Body: Forged Bronze
Stem: Brass
Press Ring: Brass
Ball: Brass (Chrome Plated)
Seat: Modified Teflon
®
O-rings: EPDM
Taco, Inc. will repair or replace without charge (at
the company’s option) any product or part which
is proven defective under normal use within three
(3) years from the date of start-up or three (3)
years and six (6) months from date of shipment
(whichever occurs first).
In order to obtain service under this warranty, it is
the responsibility of the purchaser to promptly
notify the local Taco stocking distributor or Taco
in writing and promptly deliver the subject prod-
uct or part, delivery prepaid, to the stocking dis-
tributor. For assistance on warranty returns, the
purchaser may either contact the local Taco
stocking distributor or Taco. If the subject product
or part contains no defect as covered in this war-
ranty, the purchaser will be billed for parts and
labor charges in effect at time of factory exami-
nation and repair.
Any Taco product or part not installed or operat-
ed in conformity with Taco instructions or which
has been subject to misuse, misapplication, the
addition of petroleum-based fluids or certain
chemical additives to the systems, or other
abuse, will not be covered by this warranty.
If in doubt as to whether a particular substance is
suitable for use with a Taco product or part, or for
any application restrictions, consult the applica-
ble Taco instruction sheets or contact Taco at
[401-942-8000].
Taco reserves the right to provide replacement
products and parts which are substantially simi-
lar in design and functionally equivalent to the
defective product or part. Taco reserves the right
to make changes in details of design, construc-
tion, or arrangement of materials of its products
without notification.
TACO OFFERS THIS WARRANTY IN LIEU OF
ALL OTHER EXPRESS WARRANTIES. ANY
WARRANTY IMPLIED BY LAW INCLUDING
WARRANTIES OF MERCHANTABILITY OR
FITNESS IS IN EFFECT ONLY FOR THE
DURATION OF THE EXPRESS WARRANTY
SET FORTH IN THE FIRST PARAGRAPH
ABOVE.
THE ABOVE WARRANTIES ARE IN LIEU OF
ALL OTHER WARRANTIES, EXPRESS OR
STATUTORY, OR ANY OTHER WARRANTY
OBLIGATION ON THE PART OF TACO.
TACO WILL NOT BE LIABLE FOR ANY SPE-
CIAL, INCIDENTAL, INDIRECT OR CONSE-
QUENTIAL DAMAGES RESULTING FROM THE
USE OF ITS PRODUCTS OR ANY INCIDENTAL
COSTS OF REMOVING OR REPLACING
DEFECTIVE PRODUCTS.
This warranty gives the purchaser specific rights,
and the purchaser may have other rights which
vary from state to state. Some states do not
allow limitations on how long an implied warranty
lasts or on the exclusion of incidental or conse-
quential damages, so these limitations or exclu-
sions may not apply to you.
LIMITED WARRANTY STATEMENT
TACO, INC., 1160 Cranston Street, Cranston, RI 02920    Telephone: (401) 942-8000    FAX: (401) 942-2360.
TACO (Canadá), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8.    Telephone: 905/564-9422.    FAX: 905/564-9436.
Visit our web site at: http://www.taco-hvac.com
Printed in USA
Copyright 2014
TACO, Inc.