ITEM NO. MODEL NO.
Product Specifications
Max. Operating Pressure ..................................300 PSI (2100 kPa)
Max. Shutoff Pressure .........................................125 PSI (875 kPa)
Max. Ambient Temp. ..........................................135˚F
Fluid Temp. Range ...............................................20-220˚F (-7˚-104˚C)
Service .........................................................................Water or Water/Glycol up
..........................................................................................to 50% Glycol Close Systems
Ball Rotation Speed .............................................(90˚ turn), Approx. 5 seconds
Electrical Rating .....................................................24 VAC, 60Hz, 0.48 Amps
Power Consumption ..........................................11.4 W, 0.48 Amps
Power Consumption ..........................................1.44W, 0.06 Amps
Heat Anticipator Setting ..................................0.5 Amps
End Switch Rating ................................................1 Amp @ 24 VAC
Materials of Construction
Actuator:
Body ..............................................................................High Performance
..........................................................................................Engineered Polymer
Gears .............................................................................High Performance Internally
..........................................................................................Lubricated Engineered Polymer
Valve: .............................................
Body .............................................................................. Forged Brass
Stem ..............................................................................Brass
Press Ring ..................................................................Brass
Ball ..................................................................................Brass (Chrome Plated)
Seat ................................................................................Modified Teflon®
O-Rings ....................................................................... EPDM
(After charge time)
(Open system — option available)
A
D
C
F
E
B
G
H
Zone Sentry
Dimensions:
FOR REFERENCE PURPOSES
Valve Size
A B C D E (Sweat/Press) E (Threaded) F G H (3-way)
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm
1/2” 3” 76.2 2.375” 60.3 4.125” 104.7 3.06” 77.72 3.125” 79.3 4.750” 120.6 1.562” 39.7 2.312” 58.7 5.06" 128.5
3/4” 3” 76.2 2.375” 60.3 4.125” 104.7 3.12” 79.25 3.125” 79.3 3.312” 84.1 1.562” 39.7 2.312” 58.7 5.37" 136.4
1” 3” 76.2 2.375” 60.3 4.125” 104.7 3.12” 79.25 3.875” 98.4 3.875” 98.4 1.875” 47.6 2.312” 58.7 5.50" 139.7
Inverted Flare 3/4” sweat fitting
3” 76.2 2.375” 60.3 3.5” 99.1 3.06” 77.72 7.375” * 187.33 3.5” ** 88.9 1.75” 44.5 3.312” 58.7 N/A N/A
1/2”, 3/4”, 1” Press Connect
3” 76.2 2.375” 60.3 4.125” 104.7 3.12” 79.25 6.2*** 157 N/A N/A 3.1 78.5 2.312” 58.7 N/A N/A
NPT
Models
2-Way
Sweat
Models
Z050T2 1/2" 2-way Z050C2
Z075T2 3/4" 2 way Z075C2
Z100T2 1" 2-way Z100C2
NPT
Models
3-Way
Sweat
Models
Z050T3 1/2" 3-way Z050C3
Z075T3 3/4" 3-way Z075C3
Z100T3 1" 3-way Z100C3
* Includes inverted flare fitting ** Less fittings *** Press Dimension
Valve
Size
2-Way
Cv (Kv) / Ft of
Pipe Equiv. †
Close-Off
Pressure
(kPa)
3-Way
Cv (Kv) / Ft of
Pipe Equiv. †
1/2” 4.9 (4.3) / 9.5
0-125 psi (0-862 kPa) 1.5 (1.3) / 111
1/2" Press 3.4 (2.9) / 19.6
3/4” 10.3 (8.9) / 8.4
0-125 psi (0-862 kPa) 3.3 (2.8) / 82
3/4" Press 9.5 (8.1) / 9.9
1 8.9 (7.7) / 47.4
0-125 psi (0-862 kPa) 3.0 (2.6) / 411
1" Press 7.5 (6.4) / 66.8
Inverted Flare
3/4" SWT
3.5 (3.0) / 72.9 0-125 psi (0-862 kPa) N/A
Application:
Taco Zone Sentrzone valves provide on-off, normally open or normally closed
control in closed hydronic systems. (See Geo-Sentry for open system application)
The valves can be used in a wide variety of heating and condensing cooling
applications, primarily designed for use with baseboad, fan coils, radiators,
convectors, air handlers, heat pumps and radiant applications.
Zone Sentr
(Charging)
(Power On)
Press
Connect
Size
Inverted
Flare
Z050P2 1/2" ---
Z075P2 3/4" Z075F2
Z100P2 1" ---
All models shown are normally closed. Consult factory for additional model numbers
At 4’ per second (Max. recommended residential ow rate)