Installation Instructions

Table Of Contents
24 Configuration SCADA Gateway Installation and Configuration Manual
© Tait Limited May 2017
10. Select the SCADA protocol that is in use from the drop down menu,
and enter the SCADA address of the RTU to which the TD9300 data
terminal is connected. If only IP is being used, select None.
11. In the Port field, enter the TCP port number.
12. Click Save.
13. Repeat Step 2 to Step 12 as required.
3.3.3 Configuring the SCADA Gateway
1. Select Settings > Local Parameters and click Edit.
2. In the General area, enter the name of the SCADA gateway.
3. In the Network Connection area, enter the IP address of the SCADA
gateway, and the same subnet mask and default gateway IP
addresses as entered on the DMR Node WebUI under Settings >
Local Parameters > Network Connections.
4. In the Network Checks area, enter the IP addresses of up to two
network elements to run checks that the SCADA gateway is
connected to them. At least one entry is required. For example, enter
the IP address of the Ethernet switch to which the SCADA Gateway
is connected.
5. In the Node Connection area, add the DMR network node IP
addresses as required.
6. In the SNMP area, click on ‘click to download’ if MIBs are required,
and optionally enter the SNMP community string and the IP
addresses for up to two recipients of SNMP traps.
7. In the NTP area, enter the IP address of the NTP source if required.
8. Configure Logging as required:
a. Select the logging level from the drop-down menu.
b. Enter up to two IP addresses for external syslog collection.
c. Select the Syslog protocol from the drop-down menu.
d. Select the level of alarms to be sent to the syslogger(s) from the
Syslog severity drop-down menu.
9. In the License area, click the Upload button to select a license file to
upload.
10. Click Save.
11. Select Settings > Network Parameters and click Edit.
12. Edit the Timers area as required, or accept the default settings.