Replacement Parts List

Maintenance sheet
68B166-1
B. Error codes
031: Incorrect DIPswitch setting
Check the DIPswitch settings on the PCB. Refer to Section D.
101: Warning for the “991” error code
Check the gas type of the house (and/or the building).
Check if there is any blockage in the intake air and/or exhaust. Refer to the “Venting
instructions” of the Installation manual.
If the water heater is installed as a direct-vent system, check whether there is enough
distance between the intake air terminal and the exhaust terminal. Refer to the “Vent
termination clearances” of the Installation manual.
Check the total vent length. Refer to the "Venting instructions" of the Installation manual.
Check the altitude/elevation of area of where the water heater is installed. Refer to the
“High-altitude function” of Section D. And change the DIPswitch settings.
Check if there is grease and/or dirt in the burner (Part #101) and the fan motor
(Part #103), especially if the water heater has been installed in a contaminated area.
Check if there is dust and lint in the heat exchanger.
Check the manifold pressure of the water heater. Refer to the Installation manual of the water heater.
111: Ignition failure
1. Check the gas supply and inlet gas pressure.
2. Check if the Hi-limit switch (Part #412) is properly functioning.
3. Check for connection/breakage of wires (Part #413, 708, 709, 710, 712), and/or soot on the
flame rod (Part #108). And then if the O.H.C.F (Part #413) has a breakage, Consult the
manufacturer.
4. Check if there is a buzzing spark ignition sound coming from the burner (Part #101)
when water heater prepares for combustion.
5. Listen for the double “clunk” sound coming from the gas valve assembly (Part #102)
when water heater goes into combustion.
6. (Only if sparking and/or kick sound) Check the voltage on each wire to gas valve assembly
(Part #102) and/or the igniter assembly (Part #711). Refer to Appendix A in Section C.
*No sparking sound >>>>> Refer to #1 at Appendix A in Section C.
*No kick sound >>>>> Refer to #2 at Appendix A in Section C.
7. Check if there is leaking from the heat exchanger (Part #401).
8. Check if there is dust and lint in nozzles of the manifold (Part #102).
9. Check the current on the flame rod (Part #108). Refer to #3 at Appendix Ain Section C.
121: Loss of flame
1. Check the gas supply and inlet gas pressure.
2. Check if the Hi-limit switch (Part #412) is properly functioning.
3. Check for connection/breakage of wires (Part #413, 708, 709, 712), burn marks on the
computer board (Part #701), and/or soot on the flame rod (Part #108). And then if the
O.H.C.F (Part #413) has a breakage, Consult the manufacturer.
4. Check if there is leaking from the heat exchanger (Part #401).
5. Check if there is dust and lint in nozzles of the manifold (Part #102).
6. Check the current on the flame rod (Part #108). Refer to #3 at Appendix A in Section C.
311,321,341*: Disconnected/short-circuited thermistor
Check for connection/breakage of wires and/or debris on the thermistor (Part #407, 408, 715, 718).
Check the thermistor resistance. Refer to Appendix D” in Section C.
391: Air-fuel ratio rod failure
Check for connection/breakage of wires (Part #709) and/or soot on the flame rod (Part #108).
510,551: Abnormal main gas solenoid valve and gas solenoid valve
Check for connection/breakage of wires (Part #708) and/or burn marks on the computer
board (Part #701).
Reset power supply of the water heater.
Check the voltage of each valve on the gas valve assembly (Part #102). Refer to
Appendix C” in Section C.
611: Fan motor fault
Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or
burn marks on the computer board (Part #701).
Check for frozen/corrosion of connectors of the fan motor (Part #103).
Check the voltage between blue wire and each wire of the fan motor (Part #103). Refer to
Appendix B” in Section C.
701: Computer board fault
Check for connection/breakage of wires (Part #714), and check the resistance between
white wire and red wire. Refer to Appendix A” in Section C.
711: Gas solenoid valve drive circuit failure
Refer to the “111” and “121” error codes in this section.
721: False flame detection
1. Clean the flame rod (Part #108).
2. For indoor models, check if a condensate drain is installed on the vent collar of the water heater.
3. Check if there is leaking from the heat exchanger (Part #401).
741: Miscommunication between water heater and remote controller
1. Check the model type of the remote controller. Model No. 9008172005 (TM-RE40) is the correct one.
2. Inspect the connections between the water heater and remote controller. Refer to the
“Remote controller connections” of the Installation manual.
3. Check the power supply of the water heater.
4. If this error code appears only on the green LED in the PCB (Part #701), check the voltage
on the remote controller terminal on the PCB. Refer to Appendix E” in Section C.
5. If this error code appears only on the remote controller, replace the PCB (Part #701).
6. If this error code appears on both the PCB (Part #701) and the remote controller, replace
the remote controller.
751*: Miscommunication between water heater and temperature controller
1. Check the power supply of the water heater.
2. If this error code appears only on the green LED in the PCB (Part #701), check the voltage
on the remote controller terminal on the PCB. Refer to Appendix E” in Section C.
3. If this error code appears only on the temperature controller, replace the PCB (Part #701).
4. If this error code appears on both the PCB (Part #701) and the temperature controller,
replace the temperature controller.
941*: Abnormal exhaust temperature (Only 240 (T-H3J) and 340 (T-H3S)
Indoor models)
Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or
burn marks on the computer board (Part #701).
Check the exhaust thermistor resistance. Refer to "Appendix D" in Section C.
991: Imperfect combustion
Refer to the “101” error code in this section.
C. Wiring diagram and check point of the water heater
Appendix A (For error code 111)
Check the following points during ignition stage.
# 1. Refer to check point “B” on the wiring diagram above.
Check the voltage between purple wires.
(Normal: 108 to 132 VAC)
This check point is normal?
Yes >> Replace the igniter assembly (Part #711).
No >> Go to Next.
# 2. Refer to check points “C” and “H1” on the wiring diagram above.
Check the voltages below:
C: Between blue wire and light blue wire (#3).
(Normal: 93 to 120 VDC)
C: Between blue wire and orange wire (#53).
(Normal: 93 to 120 VDC)
H1: Check the voltage between white wire and red wire.
(Normal: 1 to 15 VDC)
These check points are normal?
Yes >> Replace the gas valve assembly (Part #102).
No >> Replace the PCB (Part #701).
# 3. Check the current through the yellow flame rod wire (Part #709).
(Normal: more than 5 μA)
This check point is normal during operation?
Yes >> Replace the PCB (Part #701).
No >> Replace the flame rod (Part #108).
Appendix B (For error code 611)
Refer to check point “G” in the diagram to the left and the following.
 
Check the voltage between red wire and blue wire.
(Normal: 132 to 192 VDC)
 
Check the voltage between yellow wire and blue wire.
(Normal: 13 to 17 VDC)
 
Check the voltage between orange wire and blue wire.
(Normal: 2.0 to 6.5 VDC)
All check points are normal?
Yes >> Replace the fan motor (Part #103).
No >> Replace the PCB (Part #701).
Appendix C (For error code 510 and 551)
Refer to check point “C” in the diagram to the left and the following.
Check the voltage on each valve on the gas valve assembly.
 
Between blue wire and light blue wire (#3) (Normal: 93 to 120 VDC).
 
Between blue wire and green wire (#9) (Normal: 93 to 120 VDC).
 
Between blue wire and orange wire (#53) (Normal: 93 to 120 VDC).
 
Between blue wire and red wire (#73) (Normal: 93 to 120 VDC).
All check points are normal?
Yes >> Replace the gas valve assembly (Part #102).
No >> Replace the PCB (Part #701).
Appendix D (For error code 311, 321, 341, and 941)
 
Outlet thermistor (Find the marking of No.113 on the connector)
Check point “E1”
 
Inlet thermistor (Find the marking of No.42 on the connector)
Check point “E2”
 
Check the resistance between black wire and black wire.
Exhaust thermistor
Check point “K1”
 
Check the resistance between white wire and white wire.
All check points are normal?
Yes >> Replace the PCB (Part #701).
No >> Replace the thermistor (Part #407, 408, 718).
If the error code is indicated on the green LED (Refer to Section C) on the PCB (Part #701) of
the water heater (and/or the remote controller), refer to Section B.
<< It takes long time to get hot water at the fixtures >>
The time it takes to deliver hot water from the water heater to your fixtures depends
on the length of piping between the two. The longer the distance or the bigger the
pipes, the longer it will take to get hot water.
If you would like to receive hot water to your fixtures quicker, you may want to
consider a hot water recirculation system.
<< The water is not hot enough or turns cold and stays cold >>
Compare the flow and temperature. Refer to the “Output temperature chart” of the
Installation manual.
Check cross plumbing between cold water lines and hot water lines.
Check if the gas supply valve is fully open, the gas line is sized properly and the gas
supplies enough pressure. Refer to the “Gas supply and gas pipe sizing” of the
Installation manual.
Check the set temperature, and change the set temperature with the remote controller
or the DIPswitch setting. Refer to Section D.
Refer to the “Water circuit” in this section.
<<The water is too hot>>
Check the set temperature, lower setting temperature.
<<The hot water is not available when a fixture is opened>>
Refer to the “Power supply circuit” and Water circuit in this section.
<<Fluctuation in hot water temperature>>
Check if the filter on the cold water inlet is cleaned (Part #406).
Check if the gas line is sized properly and the supply gas pressure is sufficient.
Check for cross connection between cold water lines and hot water lines.
Refer to the “Water circuit” in this section.
<<Unit does not ignite when water goes through the water heater>>
Refer to the “Power supply circuit” and Water circuit in this section.
If you use the remote controller, turn the power button on and then check if the STAND BY LED will light up.
Check if the filter on the cold water inlet is cleaned (Part #406).
Refer to the “Water circuit” in this section.
A. Troubleshooting
<<The fan motor is still spinning after operation has stopped>>
This is normal. After operation has stopped, the fan motor keeps running from 15 to 70
seconds in order to re-ignite quickly, as well as purge all the exhaust gas out of the flue.
<<Abnormal sound from water heater>>
An abnormal sound from the water heaters is caused by not enough air supply or wrong
installations. The water heater needs more combustion air. Refer to the “101” error code
in the section B.
<<Power supply circuit>>
1. If the remote controller is installed, press the “ON/OFF” button of the remote controller, and
make sure that the STAND BY LED next to the “ON/OFF” button of the remote controller is lit.
Restart the water heater.
2. Check if the green LED on the PCB (Part #701) of the water heater is lit. If so, the power
supply circuit of the water heater is under normal condition. Next, refer to the
“Water circuit” in this section.
3. Check the fuse on the surge box (Part #703), and if it has a brown spot, need to replace it.
4. Check the power supply, and make sure that the water heater has 120 VAC.
5. If the green LED on the PCB (Part #701) isn’t lit, some electrical parts can be broken. Consult
the manufacturer.
<<Water circuit>>
1. If you use the remote controller, turn the power button on and then check if the
STAND BY LED will light up.
2. Open all hot water faucets, and make sure that there is enough water flow. This
water heater needs at least 0.5 GPM water flow (at the default set temperature) to operate.
3. Check for reverse connection and cross connection.
4. Check if the filter on the cold water inlet is cleaned (Part #406).
5. Check if there is no debris or obstruction on the fixtures.
6. Check if water ways in the water heater are frozen. If so, unfreeze them. And refer to
the Installation manual to protect your water heater from freezing.
7. Check if the inlet water pressure is higher than 40 psi. And if it’s lower than 40 psi, need
to increase the pressure.
8. Check for connections and breakage of wires (Part #402).
9. Check if the motor drive of the flow adjustment valve (Part #402) is locked due to scale
buildup, and/or water leakage. If so, Consult the manufacturer.
Temperature
°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
Resistance 15.4 12.6 10.3 8.5 7.0 5.9
ATH3J, ATH3S
Model type*
OFF
ON
1 2 3 4 5 6 7 8 9 10
OFF
ON
1 2 3 4 5 6 7 8 9 10
Outdoor models
Indoor models
D. DIPswitch settings on the computer board of the water heater
Locate the bank of DIPswitches at the bottom left of the computer board of the unit.
Change the DIPswitch settings when the power supply is turned off.
The dark square is the direction the DIPswitch should be set to. DEFAULT is the factory setting.
Temperature set
120 °F (49 °C)
DEFAULT
140 °F (60 °C)
OFF
ON
1 2 3 4 5 6
7 8 9
10
OFF
ON
1 2 3 4 5 6 7 8 9 10
W: WHITE
R: RED
BK: BLACK
P: PURPLE
LB: LIGHT BLUE
BL: BLUE
G: GREEN
Y: YELLOW
O: ORANGE
BR: BROWN
DIPswitches
9
8
7
65
4
3
21
10
OFF
Remote controller
R
BK
R
W
BK
Ground
G
O
W
Y
BL
O
R
PCB
W
120 VAC
G
Ground
SW
Ground
W
BK
G
Igniter rod
P
73
53
9
3
O
R
G
LB
BL
O.H.C.F
BL
Hi-
limit
Switch
BL
Gas
Propor-
onal
Valve
W
R
BL
BL
BL
BL
P
BK
BK
W
BK
BK
Outlet thermistor
Inlet thermistor
Surge
box
Hi-limit switch
for exhaust
Exhaust
thermistor
W
W
W
W
BK
W
BL
R
BK
Temperature controller
Heater
Heater
Heater
240/340 Outdoor Only
Heater
BK
DIPswitches
Y
Y
Y
Y
Y
Y
W
W
W
Y
Flame rod
AFR rod
BK
W
Thermostat
Heater
Heater
Heater
240/340 Indoor Only
Decrease buon
Increase buon
MIN buon
MAX buon
Green LED
SV3
SV2
SV1
MV
IG
Flow
Adjust-
ment
Valve
Flow
Sensor
FM
Indoor Only
240/340
Only
240/340 Indoor
B
C
C2
C1
G
A
A1
A2
B1
F
J
H2
E1
H1
E2
I
K2
K1
Temperature
°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
Resistance 19.5 15.9 13.0 10.7 8.9 7.4
Gas type*
Propane
OFF
ON
1 2 3 4 5 6 7 8 9 10
Natural
Gas
OFF
ON
1 2 3 4 5 6 7 8 9 10
*Factory setting
*The 341, 751 and 941 error codes are applied to the 240 (T-H3J)
and 340 (T-H3S) Indoor models only.
L
Set DIPswitches shown in the table above depending on the vent length.
Vent settings (Indoor models only)
3" venting
5 to 20 ft (DEFAULT) 21 to 40 ft 41 to 70 ft
4" venting
5 to 50 ft (DEFAULT) 51 to 100 ft N/A
OFF
ON
1 2 3 4 5 6 7 8 9 10
OFF
ON
1 2 3 4 5 6 7 8 9 10
OFF
ON
1 2 3 4 5 6 7 8 9 10
High-altitude function
Indoor models
Outdoor models
DEFAULT DEFAULT
Up to 2,500 ft Up to 2,000 ft
Up to 5,000 ft Up to 4,000 ft
Up to 7,500 ft Up to 6,000 ft
Up to 10,100 ft Over 6,000 ft
Consult the
manufacturer
FM speed is increased automatically.
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
OFF
ON
1 2 3 4 5 6 7
Appendix E (For error code 741 and 751)
Error code 741: Refer to check point “F” on the wiring diagram above.
Error code 751 : Refer to check point L” on the wiring diagram above.
Check the voltage on the remote controller and/or temperature controller
on the PCB.
Between black wire and white wire. (Normal: 11 to 25 VDC)
This check point is normal?
Yes >> Replace the remote controller and/or temperature controller.
No >> Replace the PCB (Part #701).

Summary of content (2 pages)