Description/Application
Designed specifically for heavy-duty commercial applications. Fully modulating, gas-fired, tankless, on-demand water heater
with sealed combustion (optional) and power-vented flue. Can be installed either indoors or outdoors.
Supplies hot water to: domestic hot water systems (directly or indirectly using water storage tanks), recirculations systems,
hydronic heating systems, radiant floor heating systems, and/or combined domestic & heating applications, etc.
Local codes indictate proper compliance. Please check with all local codes prior to installation.
Fuel: NG or LP
Built in Freeze Protection
Manual Reset Hi Limit (Set at 194°F)
Overheat Cut Off Fuse
Inlet, Outlet & Thermistors for Constant Temperature
Monitoring
Air-Fuel Ratio Rod
GFI, Fuse & Surge Absorber
Flame Sensor
Safety Features
5” Category III Stainless Steel
Vertical or Horizontal Installation
50’ Max Length, 5 elbows max
(90° elbows = 5’ equivalent length)
Power Vent
Electronic Ignition
5” Combustion Air Intake (with optional kit)
56 dB Noise Level at Max Output
Venting and Combustion
TM-MC01 Multi-Unit Controller (Multi-Unit System)
TM-RE30 Temperature Remote Control (optional)
- 400’ Max Distance From Water Heater
- Non-Polarized 18 Gauge Control Wiring
TM-DV50 Direct Vent Conversion Kit (optional)
TM-PC50 Pipe Cover (optional)
TM-VC50 Vent Cap (optional)
TM-BF50 Backflow Preventer (optional)
Accessories
Dip Switch: 100°F 115°F 120°F (default) 135°F 145°F 155°F 165°F 185°F
Default Mode: 100°F
105°F 110°F 115°F 120°F (default) 125°F 130° 135°F 140°F 145°F 150°F
155°F
160°F 165°F 170°F 175°F
High Temp Mode: 110°F 115°F 120°F (default) 125°F 130°F 135°F 140°F 145°F 150°F 155°F 160°F
165°F 170°F 175°F 180°F 185°F
°
Temperature Settings
Takagi Industrial Co. USA, Inc.
5 Whatney Irvine, CA 92618
888.882.5244 www.takagi.com
02-008-2010
T-M50 Flow Rate Vs. Temperature Rise
Flow Rate (gpm)
Temperature Rise (°F)
Flow Rate (gpm)
Pressure Loss (psi)
Head Feet
Above shown rate is based on single unit only
T-M50 Pressure Loss
TM-RE30 Remote Controller
Set temperature of 145° or lower Set temperature of 150° or higher
0
25
45 65 85
105
125 145
2
4
6
8
10
12
14
16
10.0
5.0
0.0
0
20
40
15
25
0
10
10
20
30
50
5
15.0
Set temperature of 145° or lower Set temperature of 150° or higher
L
W