Product Brochure

27
Capacity: 200 ampere, 600 volts a.c.
Application: Single phase, 3 wire, 1, 2 or 3 phase, 3 wire, 3 phase, 4 wire wye or delta
Enclosures: Outdoor enclosure #16 gauge galvannealed steel with polyester powder coat finish.
Block Assembly: Glass fiber reinforced polyester. High strength arc and track resistant.
Bypass: Lever-arm bypass with jaw tension release. Cover cannot be closed with lever in bypass position. NOTE: Bypass is not for use as
a circuit interrupter.
Terminals: Stud-type terminals with lay-in or stud-type load terminals. Stud-type terminals are 3/8” - 24, zinc-plated steel studs with
Belleville washer nut assemblies for copper or aluminum lugs with up to 1/2” thick mounting tongue. Recommended lugs:
Talon numbers 57606, 57606-1, 55890, 55890-1, 58022. Lay-in type terminals with dome point screws are for copper
or aluminum wire from #1 AWG to 350 MCM.
UL: All units are UL listed.
Safety Shield: Track resistant polycarbonate safety shield provides protection against accidental shorts and shocks.
GENERAL INFORMATION:
CONNECTIONS:
Type HQ-4-2W or HQ-4SW
Type HQ-7-2W or HQ-7SW
Product Schedule 425