Product Brochure
45
Capacity: 400 or 480 ampere continuous, 300 volts a.c.
Application: For use with 3 wire single phase.
Enclosures: Constructed of 14 gauge G90 steel suitable for indoor or outdoor installation. All enclosures are NEMA type 3R.
Bypass: Separate manual type #H56495.
Blocks: Glass fiber reinforced polyester plastic. High strength, arc and track resistant.
Terminals: 1/2” cold headed cadmium plated steel studs with nuts and captive Belleville washers to accommodate various pressure type
lugs for conductors from #6 to 800 KCMIL.
Hubs: No hub. 3”, 3-1/2”, 4” removable type.
UL: Type K-4UT devices are UL listed.
GENERAL INFORMATION:
TORQUE DATA:
Connection Part No. Stud Size Wrench Size Torque
Lug Mounting H56271 1/2” - 20 3/4” Hex 500 in-lbs.
Nut/Washer
Meter Mounting H56271-2 5/16” - 24 1/2” Hex 150 in-lbs.
Nut/Washer
Lug Wire - - 5/16” Allen 275 in-lbs.
Binding Screws 3/8” Allen 375 in-lbs.
1/2” Allen 500 in-lbs.
K-Base Torque Specifications
NUT WITH
BELLEVILLE
WASHER
FLAT
WASHER
Install Flat Washer On Top
Of Connector Lug
K-BASE BYPASSES:
K-4 Bypass #56495, 2 required. For use
when removing meter from K-4 mounting
device.
1. Loosen nuts “C” and “D” 4 full turns.
2. Place bypass under nuts, shorting
across from line to load side.
3. Tighten all nuts securely.
Product Schedule 443
K-4 Bypass H56495
CONNECTIONS:
Lug Group Option A
For two conductors/terminal
Optional Lugs
For two conductors/terminal
Lug H56426 (1 req.)
(#6-350 MCM)
Lug H56427 (2 req.)
(#6-350 MCM)
Lug H56733 (2 req.)
(250-800 MCM)
Lug H56476 (2 req.)
(250-800 MCM)
Lug H56477 (2 req.)
(250-800 MCM)
Lug H56425 (2 req.)
(#6-350 MCM)
Ground Lug
Included
Ground Lug
Included
Group A
Overhead
Service
Overhead
Service
Underground
Service
Group A
Underground
Service