Manual
Table Of Contents
- 1. Getting started
- 2. Operation overview
- 3. Connections- 3.1. Safety instructions
- 3.2. Safe and correct soldering
- 3.3. Avoiding irreparable damage to the decoder!
- 3.4. Pin assignment LD-G-43 | Front side
- 3.5. Pin assignment LD-G-43 | Rear side
- 3.6. Using decoders with interface connectors
- 3.7. Use of the LD-G-43 in locomotives with AC motor
- 3.8. Mounting decoders without interface
- 3.9. Connecting LEDs to the function outputs
- 3.10. Connecting inductive loads
- 3.11. Connecting the switching inputs
- 3.12. Connecting a backup capacitor or buffer circuit
- 3.13. Connection of a SUSI module
- 3.14. Completion
 
- 4. Programming
- 5. Configuration variables and registers- 5.1. Overview configuration variables LD-G-43
- 5.2. Basic settings
- 5.3. Setting the address
- 5.4. Setting the motor control
- 5.5. Function mapping
- 5.6. Effects of the outputs
- 5.7. Settings for the switching inputs
- 5.8. RailCom and DCC-A settings
- 5.9. Settings for driving operation
- 5.10. Settings for analogue mode
- 5.11. Sensivity of the overload protection
- 5.12. Auxiliary functions
- 5.13. Information
 
- 6. Checklist for troubleshooting and error correction
- 7. Technical data
- 8. Warranty, EU conformity & WEEE
tams elektronik
tams elektronik LD-G-43
6.4. Problems when switching functions
An additional device / lighting does not react to switching commands. 
Possible cause: 
 The assignment of the functions to the output to which the device / lighting is connected is
different than intended. à Check the settings in the Function Mapping.
 The   accessory   is   defective   or   incorrectly   connected.  à Check   the   accessory   and   the
connection. 
 The output is defective (e.g. due to overload or a short circuit). à Send in the decoder for
checking / (chargeable) repair. 
The light goes on and off when switching up the speed levels or the light cannot be
switched on or off. 
Possible cause: 
 The DCC speed mode of the decoder and the digital control unit do not match. Example:
The control unit is in 28 speed level mode, but the decoder is in 14 speed level mode.
à Change the speed mode on the control unit and / or on the decoder.
6.5. Problems when switching via the switching input 
No function is triggered after passing a permanent magnet in the track. 
Possible causes: 
 The reed contact or the Hall sensor is connected incorrectly. à Check the connection.
 The distance to the magnet is too great or the magnet is too weak. à Change the position
of the magnet (if possible) or insert a stronger magnet.
 The magnet is installed with the wrong polarity. à Change the installation direction. 
 The assignment of the function to the switching input is wrong.  à Check the entries in
CV 105-108.
 The minimum switch-on time is too short.à Check the entries in CV 97 - 98.
6.6. Problems in analogue mode
The locomotive does not run in analogue mode, the decoder does not react.
Possible cause: 
 Analogue mode is switched off. à Change the value for CV 29.
The decoder does not switch to analogue mode
(or switches over although it is still controlled digitally). 
Possible cause: 
 In CV 11 the value for the Packet Time-Out is set too high or too low.. à Change the value
and check the setting during operation.
Checklist for troubleshooting and error correction | 63










