User's Manual

Page
37
Heat Pump Systems
You must enter an Installer Password to access the EQUIPMENT SETTINGS from the Main Menu.
The following settings can be changed for Heat Pump Systems:
DEFAULT OPTION
MIN ON/OFF TIME 3 MIN 1-6 MIN
Minimum cycle time for the heat pump/auxiliary heater.
ALLOW HP+AUX ON YES NO
Allows the Heat Pump and
Auxiliary Heat to be on at the
same time.
Does not allow Heat Pump and
Auxiliary Heat to be on at the same
time (add-on configuration).
BALANCE POINTS HIGH 122°F (50°C)
-38 122°F
-39 50°C
The High Balance Point defines the outdoor temperature above which
the Auxiliary Heater is disabled. An external temperature sensor must
be installed for the Balance Points to operate.
LOW -40°F (-40°C)
-40 120°F
-40 49°C
The Low Balance Point defines the outdoor temperature below which
the Heat Pump compressor is disabled. An external temperature
sensor must be installed for the Balance Points to operate.