User's Manual

Page
41
Heat-Pump System Test
This procedure allows the installer to bypass delays associated with the minimum on/off times.
OUTPUT TESTED PROCEDURE EXPECTED RESULT
Fan
Mode = Off
Fan = change from AUTO to ON
Fan should turn on and off
1ST stage cooling
Mode = COOL
Modify the SETPOINT by at least 5°F
(3°C) below room temperature and
SELECT ENGAGE HOLD
First stage cooling should
engage
2ND stage cooling*
Remain in COOL mode
Return to the Temporary HOLD function
and SELECT ENGAGE again
Second stage cooling should
engage
1ST stage heating
Mode = HEAT
Modify the SETPOINT by at least 5°F
(3°C) above room temperature and
SELECT ENGAGE HOLD
First stage heating should
engage
2ND stage heating**
Remain in HEAT mode
Return to the Temporary HOLD function
and SELECT ENGAGE HOLD again
Second stage heating should
engage.
Heating using
Auxiliary Heat**
Remain in HEAT mode
Return to the Temporary HOLD function
and SELECT ENGAGE HOLD again
Auxiliary heating should
engage (if there are more heat
stages than cool stages)
* Only in two stage heat pump systems;
** Only with Heat-Pump systems equipped with an Auxiliary Heater.