Manual

KLR/KDR Line Reactor
Installation Instruction
INPUT
When installing the KLR/KDR Line Reactors
on the INPUT side of the Variable Frequency
Drive (VFD), please use the following
guidelines when wiring the unit:
e KLR/KDR Line Reactor is a
3-phase device and should be wired in a
series and positioned on the input side of the
VFD.
All Terminal Block connectors will
be marked. A1, B1, and C1 are the input
terminals where the 3 phases of incoming
power are to be wired. As a result, A2, B2,
and C2 are the output terminals. Units with
copper bus or ring lug terminals are not
marked. In these cases, either the upper
terminals or lower terminals can be used as
the input terminals as long as the selection is
consistent. For example, if an upper terminal
is selected as the input, all upper terminals
must be input terminals. Wiring from the
output terminals should connect to the input
of the VFD.
Refer to NEC wiring practices for
appropriate wire sizes for your application.
Power Wiring: Only use 75°C copper
conductors unless the wire connector is
marked for Al/Cu, then the use of aluminum
wire is permitted.
TCI recommends that these reactors
be wired and located as close to the front
end of the VFD as possible to have the
greatest success in both protecting the VFD
as well as mitigating line harmonics.
In standard 40°C ambient or less
installations, a clearance of 3 inches on
all sides of the reactors and its enclosure
is recommended for assisting in heat
dissipation and ample wire bending space.
is is a general guideline for typical
applications. If the reactor is being installed
next to a heat sensitive instrument or
control device, we recommend reviewing
specic requirements or heat limitations.
Line reactor heat loss information is
available on the web at www.transcoil.com.
ese reactors are designed to be
oor-mounted or wall-mounted. Large
open-style devices should be panel
mounted by incorporating a bracket that
would act as a shelf to support the reactor
and/or enclosure. When installing an open
style device in an existing control cabinet,
drive cabinet, motor control center, or
other large enclosure, the reactor should be
mounted in the lower half of the cabinet to
prevent hot spots or pockets of heat (this
typically allows better thermal dissipation
and heat convection). Reactors with ducts
must be mounted in such a way that
maximizes air ow. Reactors with ducts
are designed to be mounted vertically for
proper cooling.
Field Wiring Information
Below is the typical wiring diagram for the
3-phase reactor applied to the front end of
the Variable Frequency Drive (VFD).
Single-phase applications are acceptable,
however, it is important to size the unit
based on the single phase Full Load
Amperage of the VFD. e input and
output connections should be on terminals
A and C to ensure proper performance.
3-Phase, 600 Volt Class
UL Recognized; File E-116124
CE Marked
CSA Certied
Current-rated device
200% rated current for 3 minutes
Ambient Temperature: 40°C
Product Specications
Wiring Diagram
LOAD
LINE
C1
A1
B1*
L1
L3
L2
C2
A2
B2*
LINE REACTOR
* For single-phase applications, use coils A and C.
Isolate terminals B1 and B2.