Datasheet

CUS100ME Series
2 x 4” 100W AC-DC Power Supplies
CUS100ME Series
1
www.emea.tdk-lambda.com/cus100me
Features Benets
•100WConvectionRating •QuietOperation
•75WWith1m/sAirowat85°CAmbient •SuitableforHighAmbientTemperatureEnvironments
•ITE&MedicalCertications(2xMOPP) •SuitableforB&BFRatedEquipment
•SuitableforClassIandClassIIinstallations •FlexibleUtilisation
•ClassBConductedandRadiatedEMI •EasierSystemCompliance
,QGXVWULDO 7HVW
/('
%URDGFDVW
0HGLFDO
Specication
Model CUS100ME
InputVoltagerange - 85-264VAC(47-440Hz
(1)
).Deratelinearlyto90%loadfrom90to85VACinput
InrushCurrent(Coldstartat230VACinput) A <65A
InputCurrent(100Wload) A 1.4Aat100VACinput
HoldUpTime ms >24ms
HarmonicCompliance - EN/IEC61000-3-2ClassA.MinimumPF0.97/0.89(115/230Vac,100%load)
LeakageCurrent µA <250µAat230VAC63Hz
TouchCurrent(enclosureleakage) µA <100µA
TemperatureCoefcient %/°C ±0.02%/°C
NoLoadPowerDrawat230VACinput W <0.5W
OutputAdjustment - Noadjustment
Ripple&Noise mV(pk-pk)
<1%ofnominaloutputforoperatingtemperaturesabove0°C
At-20°C:12Vmodel<4%,15V&18Vmodel<3%,othermodels<2%
LoadRegulation mV <1%(0-100%load)
LineRegulation mV <0.5%(85-264VAC)
ShortCircuit&OvercurrentProtection % 110-190%.Hiccupmode,automaticrecovery
OvervoltageProtection V
115-140%ofstandardoutputvoltageforeachmodel,48Vmodelmax60V.
Latching(unitshutdown),cycleACinputtoreset
Efciency % Upto94%
ActiveAverageEfciency % >87%
OperatingTemperature - -20°Cto+85°C,seederatingcurvesforoperationabove+50°C
(2)
StorageTemperature °C -40°Cto+85°C
OperationalAltitude m 5000m
Humidity(noncondensing) %RH 5-95(15-90for/Foption),operationalandnonoperational
Cooling - Convection,conduction(coldplate)orforcedaircooling
(2)
WithstandVoltage VAC
InputtoGround1.5kVAC(1xMOPP),InputtoOutput4kVAC(2xMOPP),
OutputtoGround1.5kVAC(1xMOPP)
IsolationResistance MΩ >100MΩat25C&70%RH,OutputtoGround500VDC
InsulationClass - ConstructionsuitableforClassIorClassIIinstallation
Vibration(nonoperating) - 2G,10-500Hzfor1hour
Shock(nonoperating) - 30G,11mshalfsine
SafetyAgencyCertications
(3)
- IEC/EN/UL60950-1and60601-1.ES60601-1.DesignedtomeetIEC61010-1
Conducted&RadiatedEMI - EN55011/EN55032-B(Seeapplicationnotesforconditions)
Immunity - CompliantwithEN60601-1-2,2015(Ed4),seeimmunitytableonpage3
Weight g OpenFrame:180g;/U:240g;/A:255g;/B:220g
Size(WxLxH) mm Openframeversion:50.8x101.6x31.5
Warranty yrs 5
Connectors - Input:JSTB2P3-VH,Output:JSTB6P-VH
Note (1): Foroperationat400-440Hz,pleasecontactTechnicalSalesNote (2): Seewebsiteforfullderatingcurvesandallcasestyles
Note (3): EN60335-1CompliantversionsavailablesubjecttoMOQ.PleasecontactSales.
Specication parameters apply at 25°C ambient temperature unless otherwise stated