User manual

9
1.2.9 Cooling and mechanical construction
1.3.1 General
1.3.2 Serial link cable
1.3.4 AC cables
The Genesys series is cooled by internal fans. At the installation, care must be taken to
allow free air flow into the power supply via the front panel and out of the power supply via
the rear panel. The Genesys power supplies have a compact and lightweight package
which allows easy installation and space saving in the application equipment.
Accessories are delivered with the power supply or separately upon ordering. The list below
shows the possible accessories and ordering numbers.
S
TM
TM
1.3 ACCESSORIES
erial link cable, for linking power supplies by RS485 communication is provided with the
power supply.
Cable description: 0.5m length, shielded, RJ-45 type plugs, 8 contacts (P/N: GEN/RJ45).
*AC Input plug connector (Phoenix Contact, PC 6/4-STF-10,16)
* Output terminal shield
* Plastic legs for bench mounting.
AC cables are not provided with the power supply.
Refer to Table1-1 for recommended AC input cables (customer supplied). Add a non-locking
plug approved by the national safety standards of the country of usage.
1.3.3 Misc. hardware
* Strain relief forAC cord
* DB25 plug kit (AMP, 749809-9).
9
Observe all torque guidelines within this manual. Over torqueing may damage
unit or accessories. Such damage is not covered under manufacturers warranty.
CAUTION
Min 4x12AWG (3 wire plus safety ground),
stranded copper, 300V, 60 c minimum, rated for
25A. 3m max. length, outer diameter: 9~11mm.
O
Min 4x14AWG (3 wire plus safety ground),
stranded copper, 600V, 60 c minimum, rated for
15A. 3m max. length, outer diameter: 9~11mm.
O
190-240V~ , Three Phase
380-415V~ , Three Phase
AC Input Range
AC Input Cable
Table 1-1: Recommended AC input cable