4.Connect the AC wires to the terminals of the input plug supplied with the unit. To connect the
wires, loosen the terminal screw, insert the stripped wire into the terminal and tighten the
screw securely (10.7-13.4 Lb-inch.). Refer to Fig. 3-3 for details. Pay attention to connect the
wires according to the polarity marking on the plug.
5. Connect the AC input plug to the AC input connector at the power supply rear panel. Fasten
the plug to the connector using the two screwsat each side of the plug.
(Tightening torque:10.7-13.4Lb inch)
3.8 TURN-ON CHECKOUT PROCEDURE
3.8.1 General
3.8.2 Prior to Operation
The following procedure ensures that the power supply is operational and may be used asabasic
incoming inspection check. Refer to Fig.4-1 and Fig.4-2 for the location of the controls indicated in
the procedure.
1. Ensure that the power supply is configured to the default setting:
-AC On/Off switch at Off position.
-Dip switch :All positions at Down (”Off”) position.
-Sense connector : Configured to Local Sense as shown in Fig.3-5:
17
-For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default) position
(Refer to Fig.4-2, item9for location), if checkout is to be done in IEEE mode.
Fig.3-5: Sense connector default connection
1 Remote (+) sense
2 Local (+) sense
3 Not connected
4 Local (-) sense
5 Remote (-) sense
Plug P/N: MC 1.5/5-ST-3.81
(Phoenix)
t
Wire clamp screws
tightening torque: 10.7- 13.4 Lb-inch.
AC Input Plug :
3-Phase: P/N: PC6/4-STF-10,16:
Protective Ground wire
AC Line wires
Fig.3-4: AC input cover and strain relief
Fig.3-3 AC Input plug
Assembled Strain Relief
M3x8
Flat Head screws
(2 places)
L1
L2
L3
Removable cover. Remove only
to inspect AC Input wires
connection. Reinstall cover after
inspection.