7.7.3 Initialization control commands
ADR is followed by address which can be 0 to 30 and is used to access the
power supply .
Clear status. Sets FEVE and SEVE registers to zero (refer to section 7-8).
Reset command. Brings the power supply to a safe and known state:
Output voltage: zero, Remote: non-latched remote,
Output current: zero, Auto-start: Off,
Output: Off, OVP: maximum,
FOLD: Off, UVL: zero
The conditional registers (FLT and STAT) are updated, the other registers are
not changed.
Command
Sets the power supply to local or remote mode:
1. RMT 0 or RMT LOC, sets the power supply into Local mode.
2. RMT 1 or RMT REM, sets the unit into remote mode.
3. RMT 2 or RMT LLO, sets the unit into Local Lockout mode (latched remote mode).
#
Description
1
ADR n
2
CLS
3
RST
4
RMT
Returns the Remote mode setting:
1. "LOC"- The unit is in Local mode.
2. "REM"- The unit is in Remote mode.
3. "LLO"- The unit is in Local Lockout (latched remote) mode.
Returns MD MODE OPTION Status. 1 indicates installed and 0 indicates not
installed.
Repeat last command. If \<CR> is received, the power supply will repeat the
last command.
5
6
7
RMT?
MDAV?
\
54
7.7.5 Output control commands
7.7.4 ID control commands
Command
#
Description
Returns the power supply model identification as an string
Returns the software version as an ASCII string.
Returns the unit serial number. Up to 12 characters.
Returns date of last test. Date format: yyyy/mm/dd
ASCII
: LAMBDA, GENX-Y
1
2
3
4
IDN?
REV?
SN?
DATE?
Command
#
Description
Sets the output voltage value in Volts. The range of voltage value is described in
Table7-3. The maximum number of characters is 12. See the following examples
for PV n format: PV 12, PV 012, PV 12.0, PV 012.00, etc...
Reads the output voltage setting. Returns the string "n" where "n" is the exact
string sent in the PV n command. When in Local mode, returns the PREVIEW
(front panel) settings in a 5 digits string.
Reads the actual output voltage. Return 5 digits string.
Example: 60V supply sends 01.150, 15.012, 50.000, etc...
1
PV n
2
PV?
3
MV?
Reads the output current setting. Returns the string "n" where "n" is the exact
string sent in the PC n command. When in Local mode, returns the
PREVIEW (front panel) settings in a 5 digits string.
4
PC n
(See Note 1)
5
PC?
Sets the output current value in Amperes. The range of current values is
described in Table 7-4. The maximum number of characters is 12. See the
following examples for PC n format: PC 10, PC 10.0, PC 010.00, etc...