Instructions

3.4.2 Rack Mount Slides (optional):
3.4.3 Plastic Supporting legs
Use rack mount slides: General Devices P/N: CC3001-00-S160 (ordering P/N: C-300-S-116-RH-
LH) or equivalent to install the unit in a standard 19” equipment rack. Refer to Fig. 3-1 for slides
assembly instructions. Use three #10-32x0.38"(max.) screws at each side. To prevent internal
damage, use the specified screw length only.
Use the four plastic legs supplied with the unit, when the power supply is mounted on a surface or
when units are stacked without rack support. When using the plastic legs , maximum three units can
be stacked.
This power supply is fan cooled. The air intake is at the front panel and the exhaust is at the rear
panel. Upon installation allow cooling air to reach the front panel ventilation inlets. Allow minimum
10cm (4 Inch) of unrestricted air space at the front and the rear of the unit.
The power supply should be used in an area that the ambient temperature does not exceed +50 C.
The Genesys series designed for use in TN, TT and IT power distribution systems.Depending on
its input option, the Genesys 3300W series can be operated from a nominal 190V to 240V, single or
three phase, 47~63Hz or from a nominal 380V to 415V, three phase, 47~63Hz. The input voltage
range and current required for each model is specified in Chapter 2. Ensure that under heavy load,
the AC voltage supplied to the power supply does not fall below the specifications described in
Chapter 2.
3.5 LOCATION, MOUNTING AND COOLING
3.6 AC SOURCE REQUIREMENTS
3.7 AC INPUT POWER CONNECTION
o
TM
TM
Ensure that the screws used to attach the slides to the unit do
not penetrate more than 6mm into the sides of the unit.
CAUTION
CAUTION
WARNING
Connection of this power supply to an AC power source
should be made by an electrician or other qualified personnel.
The power supply shall be connected to the AC source via protective device (circuit breaker,
fuses, ...etc.) rated 30A max. for single phase models or 20A max. for three phase models.
There is a potential shock hazard if the power supply chassis
(with cover in place) is not connected to an electrical safety
ground via the safety ground in theAC input connector
14
Fig.3-1: Rack-mount slides assembly
#10-32x0.38"(max.)
screws
Tightening torque:
25.4-31.7 Lb-inch.