Data Sheet

2
LS25-150
Model Selector
Adjust Range Max Current Load Reg Line Reg Ripple Noise Efficiency
Model Voltage (V) (A) (mV) (mV) (mV) (typ) %
LS25-3.3 3.3V 2.85 - 3.6 6 66 16.5 80 72
LS25-5 5V 4.5 - 5.5 5 50 25 80 77
LS25-12 12V 10.8 - 13.2 2.1 60 60 120 79
LS25-15 15V 13.5 - 16.5 1.7 75 75 120 82
LS25-24 24V 22 - 27.6 1.1 120 120 120 84
LS25-36 36V 32 - 40 0.75 150 150 150 85
LS25-48 48V 42 - 54 0.57 180 180 200 85
LS35-3.3 3.3V 2.85 - 3.6 7 66 16.5 80 73
LS35-5 5V 4.5 - 5.5 7 50 25 80 77
LS35-12 12V 10.8 - 13.2 3 60 60 120 81
LS35-15 15V 13.5 - 16.5 2.4 75 75 120 83
LS35-24 24V 22 - 27.6 1.5 120 120 120 84
LS35-36 36V 32 - 40 1 150 150 150 84
LS35-48 48V 42 - 54 0.8 180 180 200 84
LS50-3.3 3.3V 3.0 - 3.6 10 40 20 80 75
LS50-5 5V 4.75 - 5.5 10 40 20 80 80
LS50-12 12V 10.8 - 13.2 4.2 96 48 120 84
LS50-15 15V 13.5 - 16.5 3.4 120 60 120 85
LS50-24 24V 22 - 27.2 2.2 192 96 120 86
LS50-36 36V 32 - 40 1.4 288 144 150 86
LS50-48 48V 42 - 54 1.1 384 192 200 86
LS75-3.3 3.3V 3.0 - 3.6 15 40 20 80 75
LS75-5 5V 4.75 - 5.5 12 40 20 80 79
LS75-12 12V 10.8 - 13.2 6 96 48 120 84
LS75-15 15V 13.5 - 16.5 5 120 60 120 85
LS75-24 24V 22 - 27.2 3.2 192 96 120 86
LS75-36 36V 32 - 40 2.1 288 144 150 86
LS75-48 48V 42 - 54 1.6 384 192 200 87
LS100-3.3 3.3V 3.0 - 3.6 20 66 16.5 80 74
LS100-5 5V 4.75 - 5.5 16 50 25 80 77
LS100-12 12V 10.8 - 13.2 8.5 60 60 120 81
LS100-15 15V 13.5 - 16.5 7 75 75 120 82
LS100-24 24V 22 - 27.2 4.5 120 120 120 84
LS100-36 36V 32 - 40 3 150 150 150 84
LS100-48 48V 42 - 54 2.3 180 180 200 84
LS150-3.3 3.3V 3.0 - 3.6 30 66 16.5 80 74
LS150-5 5V 4.75 - 5.5 26 50 25 80 78
LS150-12 12V 10.8 - 13.2 12.5 60 60 120 83
LS150-15 15V 13.5 - 16.5 10 75 75 120 84
LS150-24 24V 22 - 27.2 6.5 120 120 120 86
LS150-36 36V 32 - 40 4.3 150 150 150 86
LS150-48 48V 42 - 54 3.3 180 180 200 87
Notes: See page 1
(1) Switch selectable for 115 or 230VAC
(2) LS50, LS75-3.3 & -5: Derate linearly to 70% load from +50 to +70°C.
LS75-12,-15,-24,-36,-48 Derate linearly to 60% load from +50 to +70°C.
LS100-3.3 & 5 Derate linearly to 60% load from +45 to +70°C. Derate linearly to 80% load from 115V to 88VAC input.
LS100-12,-15,-24,-36,-48 Derate linearly to 60% load from +50 to +70°C. Derate linearly to 80% load from 115V to 88VAC input.
LS150-3.3 & 5 Derate linearly to 50% load from +40 to +70°C.
LS150-12,-15,-24,-36,-48 Derate linearly to 70% load from +50 to +70°C.