General Purpose Relays
1
Relay Package RT
I
Relay package consisting of RT relay, DIN-rail socket, plastic
retaining clip, module and marking tag
I
1 CO with 16 A or 2 CO with 8 A rated load
I
Sensitive DC- or AC coil
I
Reinforced insulation (protection class II / VDE 0700), safe
separation to VDE 0160
II
RoHS compliant (Directive 2002/95/EC)
as per production date code 0535
Approvals
Relay: V REG.-Nr. 6106, Z E214025
Socket: V REG.-Nr. 6106 in preparation, Z E135149
Technical data of approved types on request
Contact data 1-pole 2-pole
Contact configuration 1 CO 2 CO
Contact set single contact
Type of interruption micro disconnection
Rated current 16 A *) 8 A
Rated voltage / max.switching voltage AC 240/400 VAC
Maximum breaking capacity AC 4000 VA 2000 VA
Limiting making capacity,max 4 s, df 10% 30 A 15 A
Contact material AgNi 90/10, AgNi90/10 gold plated
Mechanical endurance DC coil > 30 x 10
6
>30x10
6
AC coil > 10 x 10
6
>5 x 10
6
Rated frequency of operation with / without load 6 / 1200 min
-1
*) For full load current (16 A) the relay terminals 11-21, 12-22 and 14-24 have to be bridged.
Contact ratings
For contact ratings see datasheet Interface Power relay RT
Coil data
Rated coil voltage range DC coil 24 VDC
AC coil 24, 230 VAC
Coil power DC coil typ 400 mW
AC coil typ 0.75 VA
Operative range 2
Coil versions, DC-coil
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
VDC VDC VDC Ohm mW
LC4 24 16.8 2.4 1440+10% 400
Coil versions, AC-coil 50Hz
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
50 Hz 50 Hz 50 Hz
VAC VAC VAC Ohm VA
R24 24 18.0 3.6 350+10% 0.76
S15 115 86.3 17.3 8100+15% 0.76
T30 230 172.5 34.5 32500+15% 0.74
All figures are given for coil without preenergization, at ambient temperature +23°C
Other coil voltages on request
F0287-A

Summary of content (3 pages)