6. VISUAL AID
Figure 7 shows a typical application of PLASTI--GRIP terminals and splices. This illustration should be used by
production personnel to ensure a correctly applied product. Applications which DO NOT appear correct should
be inspected using the information in the preceding pages of this specification and in the instructional material
shipped with the product or tooling.
FIGURE 7. VISUAL AID
WIRE INSULATION
MUST BE UNDAMAGED
CRIMP DOT CODE
MUST BE FORMED
WHEN USING TOOL
WITH COLOR CODING
WIRE INSULATION MUST BE INSIDE INSULATION
BARREL BUT MUST NOT ENTER WIRE BARREL
INSULATION BARREL MUST
BE IN FIRM CONTACT WITH
WIRE INSULATION
WIRE SIZE MUST BE SAME
AS WIRE SIZE STAM PED
ON TERMINAL
THEREMUSTBENO
NICKED OR MISSING
CONDUCTOR STRANDS
WIRE MUST BE
FULLY INSERTED
END OF CONDUCTORS MUST BE
FLUSH WITH, OR EXTEND SLIGHTLY
BEYOND END OF WI RE BARREL
END OF CONDUCTORS MUST
BE AGAINST WIRE STOP OR
MUST BE FLUSH WITH, OR
EXTEND SLIGHTLY BEYOND,
END OF WIRE BARREL
ALL CONDUCTORS MUST BE HELD
FIRMLY INSIDE WIRE BARREL
TERMINAL MUST NOT BE BENT
OR DEFORMED IN ANY WAY
CRIMP DOT CODE MUST BE
FORMED WHEN USING TOOL
WITH COLOR CODING
SPLICE MUST NOT BE
BENT OR DEFORMED
IN ANY WAY
SPLICE INSULATION MUST
BE IN FIRM CONTACT WITH
WIRE INSULATION