Installation Sheet

4
Check the System
COM X1 X2 X3 X4
After installing the entire low voltage system, if the
lamps have low intensity, then measure the voltage at
the fixture closest to the power feed contacts with a
voltmeter. The system must be at least 80% loaded and
the voltmeter should read between 11V - 12V ~AC. If
the voltage does not fall in this range, call Encompass
Lighting Group "Technical Support" at 847-410-4606.
After installing the entire system, operate the system for
five minutes. On the low voltage side, all electrical
connection points should be no more than warm to the
touch. If a connection is hot to the touch, retighten the
connection and check to ensure that the temperature
decreases.
The transformer circuit breaker will trip if there is a short
in the system. After removing the cause of the short, the
circuit breaker needs to be reset to power the system
up.
Replace the transformer cover and tighten the two
Phillips screws on the sides of the transformer.