Installation Sheet

Installation Instructions for
120 Volt to 12 Volt DC Single Feed 300W Remote
Electronic Transformers
950RM30012EL
GP I :ENERAL RODUCT NFORMATION
This transformer is ETL listed for use with low voltage lighting
systems of brands offered by Encompass Lighting Group.
This product is suitable only for indoor dry locations and
approved for use at any height above the finished floor.
A typical installation is shown. Specific installation must be in
accordance with the local electrical codes.
This product may be dimmed only with a low voltage
electronic dimmer. Using a dimmer not designed for low
voltage electronic applications may work initially, but could
eventually cause transformer failure and will void the warranty.
The dimmer must be derated as indicated by the dimmer
manufacturer.
This product is intended for use with Generation Brands low
voltage lighting systems only.
During installation, make sure all power connections are tight.
Read all instructions thoroughly. Read "Important Safety
Information" on next column before proceeding with the
installation.
Important Safety Information
Do not conceal or extend bus bar conductors through a
building wall.
To reduce the risk of fire and burns, do not install this lighting
system where the uninsulated open bus bar conductors can
be shorted or contact any conductive materials.
To reduce the risk of the system overheating and possibly
causing a fire, make sure all the connections are tight.
Do not install fixture assemblies closer than six inches to
curtains or similarly combustible materials.
Turn the electrical power off before modifying the lighting
system in any way.
The fixtures used with the system must be identified for use
with the corresponding system.
To Reduce Risk of Fire, it is important to wire the remote
transformer for the system as described in this installation
instruction.
Load the circuit of the remote transformer to 300MAXIMUM
Watt.
1
TRANSFORMERS
1.0
1.0
1.3
CAUTION - RISK OF FIRE
This product must be installed in accordance with
the applicable installation code by a person familiar
with the construction and operation of the product
and the hazards involved.
Use minimum 90°c supply conductors.