Installation Manual
Power Monitoring and Management 293
Using RACADM
racadm config -g cfgServerPower -o 
cfgServerPowerCapWatts <power cap value in Watts>
racadm config -g cfgServerPower -o 
cfgServerPowerCapBTUhr <power cap value in BTU/hr>
racadm config -g cfgServerPower -o 
cfgServerPowerCapPercent <power cap value in % >
racadm config -g cfgServerPower -o 
cfgServerPowerCapEnable <1 to enable, 0 to disable>
  NOTE: When setting the power budget threshold in BTU/hr, the conversion to 
Watts is rounded to the nearest integer. When reading the power budget threshold 
back, the Watts to BTU/hr conversion is again rounded in this manner. As a result, 
the value written could be nominally different than the value read; for example, a 
threshold set to 600 BTU/hr will be read back as 601 BTU/hr.
Viewing Power Monitoring
Using the Web Interface 
To view the power monitoring data: 
1
Log in to the iDRAC6 Web interface.
2
Select 
Power Monitoring
 in the system tree. The 
Power Monitoring 
page displays. 
The following section describes the information provided on the Power 
Monitoring page:
Power Monitoring
•
Status
: 
OK
 indicates that the power supply units are present and 
communicating with the server, 
Warning
 indicates that a warning alert was 
issued, and 
Severe
 indicates a failure alert was issued.
•
Probe Name
: System Board System Level. This description indicates the 
probe is being monitored by its location in the system.
•
Reading
: The current power consumption in Watts/BTU/hr.