5.3 Power Supply Specifications
Table 4. Power Supply Specifications
Feature Specification
Wattage
717 Watt (high output)
502 Watt (Energy Smart)
Voltage 90-264 VAC, autoranging, 47-63 Hz
Maximum inrush
current
Under typical line conditions and over the entire system ambient operating range,
the inrush current may reach 55A per power supply for 10ms or less.
5.4 Heat Dissipation
High output (717W) power supply: 2446.5 BTU/hr maximum
Energy Smart (502W) power supply: 1712.9 BTU/hr maximum
5.5 Environmental Specifications
Table 5. Environmental Specifications
Fresh Air: temperature, humidity, altitude de-rating
Continuous
operation
When operating in the expanded temperature range, system performance may be impacted,
and ambient temperature warnings may be reported on the LCD and in the System Event Log.
≤ 10% of annual operating hours: 5°C to 10°C and 35°C to 40°C (with no direct sunlight on
the equipment) at 5% to 85% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 40°C for a maximum of 10% of its annual operating hours. For
temperatures between 35°C and 40°C (95°F to 104°F), de-rate maximum allowable dry bulb
temperature by 1°C per 175m above 950m (1°F per 319 ft above 3117 ft).
≤ 1% of annual operating hours: 5°C to 5°C and 40°C to 45°C (with no direct sunlight on
the equipment) at 5% to 90% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 45°C for a maximum of 1% of its annual operating hours. For
temperatures between 40°C and 45°C (104°F to 113°F), de-rate maximum allowable dry bulb
temperature by 1°C per 125m above 950m (1°F per 228 ft above 3117 ft).
Expanded operation restrictions:
No cold startup below 5°C
Maximum altitude for the operating temperature must be 3050m (10,000ft)
Expanded
operation
-40° to 65°C (-40° to 149°F) with a maximum temperature gradation of 20°C per hour
Temperature
Operating See Fresh Air for temperature information
Storage -40° to 65°C (-40° to 149°F) with a maximum temperature gradation of 20°C per hour
Relative Humidity
Operating See Fresh Air for humidity information
Storage
5% to 95% at a maximum wet bulb temperature of 33°C (91°F); atmosphere must be
condensing at all times