Uninterruptible Power Supply ECO 0.50 ECO 0.70 ECO 0.90 ECO 1.1 ECO 1.
Index Safety Warnings ................................................................................ 2 1 Introduction ................................................................................. 3 2 General Characteristics ................................................................... 3 3 Receipt and site selection ................................................................ 4 4 EXTERNAL DESCRIPTION .................................................................. 5 4.1 4.2 Front Panel ...
Safety Warnings Read this manual carefully and completely before installing and using the TECNOWARE ECO Uninterruptible Power Supply, which, from here after, will also be referred to as UPS. This manual should be kept close to the UPS and read before the UPS is installed and used. The UPS must be used only by properly trained personnel.
1 Introduction ECO is an UPS (Uninterruptible Power Supply) specifically designed to protect your computer from any type of irregularities in the AC line (such as black-outs, under or over voltages, micro-interruptions), which often cause damage to your Hardware and Software. Under normal AC line condition, ECO filters frequently occurring electrical disturbances (such as transients, spikes, interferences, etc.
• Visual and acoustic signals indicating operating mode and alarm/fault conditions. • High efficiency • Maximum reliability • Smart design and easy to use 3 Receipt and site selection Carefully remove the UPS from its packaging, and carry out a meticulous inspection. We recommend keeping the original packaging in a secure place, in case you need to send the UPS for maintenance purposes. In case of transport damage, notify the carrier and dealer immediately.
4 EXTERNAL DESCRIPTION 4.1 Front Panel The front panel informs the user about operating status, alarm conditions through 2 leds. On the front panel there are (see figure 1): 1. The ON/OFF button: enables the user to turn ON/OFF the UPS. 2. The LINE/BATTERY led: this led (blue color) is always on during the functioning in Normal Mode, it flashes one time every 4 seconds in Battery mode and it flashes one time every second in Low Battery condition. 3.
4.2 Rear Side 3 2 1 Figure 2 – Rear Side On ECO rear side there are (see figure 2): 1. Grounded AC Input power socket: IEC C14 type; to connect the UPS to the AC utility line. 2. Input fuse: electrical specification: max current 5 A, voltage 250 V. 3. Grounded UPS Output receptacles: IEC C13 type. 5 Electrical Installation and First Start Up We advise you to follow the steps below explained for greater safety: 1.
4. Switch the UPS off (by pressing again the ON/OFF button for about 2 seconds). 5. Connect the devices to be supplied to the UPS outputs, by using only the included cables. Be sure all the devices have the main switch in ON position. 6. Turn on the UPS again. Check that it starts working correctly and it doesn’t signal any sort of anomaly. Moreover be sure that all the devices connected to the UPS outputs are working correctly. 7. Simulate a black-out by removing the AC Input line.
6.2 Battery Mode The UPS automatically runs in Battery mode if the AC Input Line voltage amplitude gets out of security limits (in case of a black-out or over-voltage/low-voltage): in this case, the UPS supplies the required output power by its internal battery and by the Inverter block. The UPS automatically returns in Normal mode a few seconds after the AC Input Line is recovered. In Battery mode the UPS emits an acoustic alarm signal every 4 seconds and simultaneously the LINE/BATTERY led flashes. 6.
7 Technical Characteristics UPS ECO Model Power Recommended for: 0.50 0.70 0.90 1.1 1.
8 Maintenance 8.1 UPS Cleaning Before starting any cleaning operation, be sure that: 1. The AC Input Voltage for the UPS has been removed. 2. The UPS is OFF. Use only a cloth dampened with water to clean the unit. If UPS works in an environmental unusually dusty or dirty, remove the dirty from the ventilation holes. Before restarting the UPS be sure it is completely dry. If any liquid gets inside the UPS, do not start the unit and contact Technical Service immediately. 8.
Battery replacement must be performed exclusively by qualified technical personnel authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded. When replacing batteries, replace with the same type and number. CAUTION: A battery can present a risk of electrical shock and high short circuit current.
9 Troubleshooting Alarms and problems you may encounter during operating the UPS are given in the table below. Apply the suggestions corresponding to each anomaly as described into the table. If your anomaly is excluded or the suggested actions do not solve your problem, consult the Technical Service. Please give the following information to the Technical Service: Model and serial number of the UPS, which can be found on the nameplate on the rear of the UPS. Description of anomaly.
Conformity to the European Directives TECNOWARE S.r.l. confirms that ECO models comply with the requirements set out in: the Low Voltage Directive (Safety) 2006/95/EC and following amendments, the EMC (Electro-Magnetic Compatibility) Directive 2004/108/EC and following amendments.
TECNOWARE s.r.l. www.tecnoware.