Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.
Index Safety Warnings ................................................................................ 2 1 Introduction ................................................................................. 3 2 General Characteristics ................................................................... 4 3 Receipt and site selection ................................................................ 4 4 EXTERNAL DESCRIPTION .................................................................. 5 4.1 Front Panel .......
Safety Warnings Read this manual carefully and completely before installing and using the TECNOWARE ERA LED Uninterruptible Power Supply, which, from here after, will also be referred to as UPS. This manual should be kept close to the UPS and read before the UPS is installed and used. The UPS must be used only by properly trained personnel.
1 Introduction ERA LED is a Line Interactive UPS (Uninterruptible Power Supply) specifically designed to protect your computer from any type of irregularities in the AC line (such as black-outs, under or over voltages, micro-interruptions), which often cause damage to your Hardware and Software. Under normal AC line condition, ERA LED performs output voltage regulation and filters frequently occurring electrical disturbances (such as transients, spikes, interferences, etc.
2 General Characteristics ERA LED has all the advanced features, which guarantee maximum reliability and safety: • All functions are controlled by a microprocessor, giving full guarantee of high reliability. • Output Voltage regulation through AVR (Automatic Voltage Regulation). • Overload protection both in normal mode and in battery mode. • High performance battery charger, which extends the battery medium life ensuring an optimal recharge.
4 EXTERNAL DESCRIPTION 4.1 Front Panel The front panel informs the user about operating status, alarm conditions and measurements. Front panel shown below consists of two parts: 1. 3 Leds that show the functioning modes, alarm and fault conditions. 2. ON/OFF button: enables the user to turn ON/OFF the UPS. 1 2 Figure 1 – Front panel UPS ERA LED 1.5 – 2-0 – 2.
4.1.1 Leds and ON/OFF Button Please refer to figure 2. 4 3 2 1 Figure 2 –LCD Display 1. Line LED: this (blue) led is always on in “LINE” mode. 2. Battery LED: this (yellow) led is on in “BATTERY” mode. 3. Fault LED: this FAULT led (red) switches on to indicate the excessive or the OVERLOAD condition or generic “FAULT”. 4. ON/OFF Button: to turn ON and OFF the UPS. User’s manual 6 UPS ERA LED 1.5 – 2-0 – 2.
4.2 Rear Side 6 6 5 5 3 3 1 2 1 2 4 4 UPS ERA LED 1.5-2.0 UPS ERA LED 2.6 Figure 2 – Rear Side 1. Grounded AC Input power socket: IEC C14 type; to connect the UPS to the AC utility line. 2. Input fuse: electrical specification: max current 10 A (ERA LED 1.5 – 2-0 -2.6), voltage 250 V. 3. Grounded UPS Output receptacles: IEC C13 type, black colour, to supply critical loads. 4. Grounded (ONLY FILTERED) Output receptacles: IEC C13 type, red colour, to supply NON-critical loads. 5.
5 Electrical Installation and First Start Up We advise you to follow the steps below explained for greater safety: 1. Switch off all the devices (Personal Computer or other electronic devices) that need to be supplied by the UPS. 2. Connect the UPS Input socket to the AC line outlet Through the Personal Computer supplying cable. It is mandatory to ground the AC line outlet according to the Safety Standards.
6 Functioning 6.1 Normal Mode The UPS typically works in Normal mode: Input mains power is available and its amplitude is within specifications. The Normal mode is identified by the lighting of Line Led in blue color. During Normal mode, the UPS recharges the batteries and keeps them in an optimal charging voltage. 6.
6.4 Load Control When the Output load is higher than nominal value the UPS warns of Overload condition by emitting a continuous acoustic alarm. The UPS warns of an Overload less than 110% by acoustic alarm. An Overload between 110% and 130% is accepted for about 30 seconds and after UPS switches automatically off. The UPS switches immediately off if the Overload is higher than than 130%. Once the requested power is back within range, the UPS switches automatically to the Normal mode.
8 Technical Characteristics UPS ERA LED Model Power Recommended for: 1.5 2.0 2.
9 Maintenance 9.1 UPS Cleaning Before starting any cleaning operation, be sure that: 1. The AC Input Voltage for the UPS has been removed. 2. The UPS is OFF. Use only a cloth dampened with water to clean the unit. If UPS works in an environmental unusually dusty or dirty, remove the dirty from the ventilation holes. Before restarting the UPS be sure it is completely dry. If any liquid gets inside the UPS, do not start the unit and contact Technical Service immediately. 9.
Battery replacement must be performed exclusively by qualified technical personnel authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded. When replacing batteries, replace with the same type and number. CAUTION: A battery can present a risk of electrical shock and high short circuit current.
10 Troubleshooting Alarms and problems you may encounter during operating the UPS are given in the table below. Apply the suggestions corresponding to each anomaly as described into the table. If your anomaly is excluded or the suggested actions do not solve your problem, consult the Technical Service. Please give the following information to the Technical Service: Model and serial number of the UPS, which can be found on the nameplate on the bottom side of the UPS. Description of anomaly.
Conformity to the European Directives TECNOWARE S.r.l. confirms that ERA LED models comply with the requirements set out in: the Low Voltage Directive (Safety) 2006/95/EC and following amendments, the EMC (Electro-Magnetic Compatibility) Directive 2004/108/EC and following amendments.