For BATTERIES REPLACEMENT, please follow the following steps:
1. With the UPS functioning in LINE mode, please force the transfer into BYPASS mode by
moving the manual BYPASS switch, positioned on the rear side, in ON (BYPASS) position.
All details are described in the Chapter “Functioning – Bypass”
2. In order to access to the HOT SWAP battery box, firstly remove the right part of the front
panel. Remove manually the panel.
3. Unscrew the screws blocking the left part of battery connector on the front side of batteries
box.
4. Unhook left part (free) of battery connector from the right one.
5. Unscrew the 4 screws at the corners of the battery box front side
6. Unhook the UPS battery cables from the battery connector located on the front side of the
battery.
7. Using the horizontal handle completely extract battery box.
8. Remove the top cover of the box by unscrewing the rear and frontal side screws in order to
gain access to the inside batteries
9. Replace the battery by refitting carefully all relevant connections.
10. Replace the top cover of the battery box – replace all cover screws.
11. Insert again the battery box into its own place.
12. Screw the 4 screws again at the corners of the battery box front side.
13. Fasten left part of the battery connector to the right part and screw all the screws blocking
the left part of the battery connector on the front side of the battery box.
14. Replace the right part of the front panel.
15. Move the manual BYPASS switch, located on the rear side, in the NORMAL position (OFF)
and wait for the return to normal functioning.
ATTENTION
DANGER OF SHORT-CIRCUIT
After having removed HOT SWAP battery box do not insert any object or any tool into
the battery box drawer in order to avoid any short-circuit risk.
The battery connection or replacement must be carried out ONLY by qualified
Technical personnel specialized and authorized by Tecnoware.
TECNOWARE declines any responsibilities if this rule is not followed.
SAFETY FOR THE OPERATOR
If the EVO RT does not have the original security characteristics, it must be made non
functional, and a non authorised use must be avoided.
The problem must then be reported to qualified technical personnel.
The original security characteristics can be lost if for example the EVO RT shows visible
damages or an anomalous running.