User`s manual
EPO (EMERGENCY POWER OFF)
EPO
1
2
Remote Button
EPO
EVO have the EPO (Emergency Power OFF) connector (2 terminals connector) on the rear. This
permits to immediately switch the UPS OFF from a distance in case of emergency.
To use EPO function is very simple: it is sufficient to connect an external switch to the EPO
terminal(see Figure 3 – Rear Side): if the switch is CLOSED the UPS works normally. If on the
contrary, the switch is OPEN then the UPS turns OFF immediately. To switch ON the UPS again
it is necessary to close the EPO switch and then manually restart the UPS from the front panel.
The EPO terminals are isolated and do not need an external feeding voltage.
REMOTE ON/OFF
ON
1
2
Remote Button ON
OFF
3
4
Remote Button OFF
The EVO models have remote ON/OFF terminals connector on the rear side (see figure 4),
this permits to switch the UPS ON and OFF from a distance. Using the ON/OFF external
button (as described in the above picture) the frontal panel button capacity can be used
from a distance.
Evo is on; pressing the OFF button connected to terminal 1 and 2 for at least 3 seconds,
EVO turns OFF.
EVO is off; pressing the ON button connected to terminal 4 and 5 for at least 3 seconds,
EVO turns ON.
The remote ON function is disabled when the UPS is off and the AC input line voltage is not
present.
User’s manual 7 UPS EVO RT