User`s manual

User’s manual 34 UPS EVO DSP TT
11 Technical Specifications
EVO DSP TT MODELS
Rating [kVA] 10 15 20 30 40 60 80 100
ENVIRONMENTAL
Storage temperature
range
-25°C to +55°C (15°C - 40°C recommended for longer battery life)
Operating temperature
range
0°C to +40°C (20°C - 25°C recommended for longer battery life)
Relative humidity range
0% - 95% (non condensing)
Max. altitude without
derating [m]
1000
Protection level
IP 20
[W]
800 960 1280 1920 2560 3840 5120 6400
[Btu]
2730 3277 4369 6553 8737 13106 17475 21843
Maximum power
dissipation
[kcal/h]
688 825 1100 1650 2200 3302 4403 5503
ELECTRICAL
Mains Input
Number of phases
3 Phases + Neutral
Nominal voltage [V]
380 / 400 / 415 (Line-Line)
187 (Line-Neutral; at 100% load)
120 (Line-Neutral; at 64% load)
Lower
limit
80 (Line-Neutral; at 42% load)
Voltage range
for Normal
mode (Line-
Neutral) [V]
Upper
limit
280 (Line-Neutral)
Nominal frequency [Hz]
50 / 60
Frequency range [Hz]
+/-10%
waveform
sinusoidal
Nominal current
[A]
RMS value
*(Note 2)
13 20 26 40 53 79 105 131
waveform
sinusoidal
Maximum
current [A]
RMS value
17 23 30 47 61 95 125 158
Output
Performance classification
according to IEC 62040-3
VFI-SS-111
Number of phases
3 Phases + Neutral
Nominal voltage [V]
380 / 400 / 415 (Line-Line)
Normal
mode
Static voltage
regulation
at %100 linear
load
Normal
mode
< 1%
Nominal frequency [Hz]
50 / 60
Free running frequency [Hz]
± 0,01%
Total Harmonic Distortion
(THD) at rated linear load
< 3%
Nominal power [kVA]
10 15 20 30 40 60 80 100
Maximum load
Power Factor
0.8
Nominal active power [kW]
8 12 16 24 32 48 64 80
Nominal current [A] at 380V
15.2 22.7 30.3 45.5 60.6 91 121 151
Load crest factor at rated
power
3:1
Overload duration
> 1 min at 150% load
Efficiency (Normal mode) at
rated linear load (Power
Factor = 0.8)
> 92%