User`s manual

UPS EVO DSP TT 5 User’s manual
2 Installation
2.1 Transportation
The UPS must remain in a vertical position throughout the transportation. Make sure that the floor can
support the weight of the system – check with building engineer if not sure.
2.2 Unpacking
Equipment and batteries whose packaging is damaged during transportation shall be
inspected by a qualified technical person before starting with the installation.
The procedure is as follows:
Remove the bands and the protective packaging from the UPS.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is
recommended to keep the original package for future needs (e.g. further transportation
or return to Service Department).
Check if the following are provided with the equipment:
Key of the cabinet door
Battery fuses (three pieces)
Test report
2.3 Storage
Recommended storage temperature, humidity and altitude values are listed in the “Technical
Specifications” section.
If the batteries will be stored for longer than 2 months, they must be charged periodically. Charge
period depends on the storage temperature. The relationship is as shown below:
Every 9 months if the temperature is below 20°C.
Every 6 months if the temperature is between 20°C and 30°C.
Every 3 months if the temperature is between 30°C and 40°C.
Every 2 months if the temperature is over 40°C.
2.4 Location and Connection of the UPS
2.4.1 Environmental Requisites
This product meets the safety requirements for devices to be operated in restricted access locations
according to EN 60950-1 safety standard, which states that the owner should guarantee the following:
Access to the equipment can only be gained by service persons or by users who have been
instructed about the reasons for the restrictions applied to the location and about any
precautions that shall be taken.