Performance Data Sheet

July 26, 2013
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA4480YNAD*
BoM: 2G734-09, -** R-134a 3/4 HP
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
H
CH
Suction
Liquid
90 F 90%
SCFM
Oz.
Lbs.
AJA4480YNADA
20.0
12.1
11.6
3/8” S
1/4” S
N/A
230
26
63
AJA4480YNADG
3/8” S
3/8” S
3.2 lbs
64
AJA4480YNADH
3/8” S
3/8” S
N/A
63
AJA4480YNADK
3/8” S
1/4” S
63
AJA4480YNADC
3/8” S
3/8” S
3.2 lbs
64
AJA4480YNADS
3/8” S
3/8” S
N/A
63
AJA4480YNADJ
3/8” S
3/8” S
3.2 lbs
64
AJA4480YNADP
3/8” S
3/8” S
3.2 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T,
80°F
90°F
100°F
110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
20
18.4
5305
875
112
4791
878
120
4300
881
128
3829
884
135
25
22.1
5883
946
116
5328
954
123
4796
962
131
4287
970
139
30
26.1
6467
1022
120
5871
1035
127
5298
1047
135
4749
1060
142
35
30.4
7051
1101
124
6413
1119
131
5800
1136
138
5209
1154
146
40
35.1
7631
1184
127
6950
1207
135
6294
1229
142
5663
1251
149
45
40.1
8201
1271
131
7550
1298
139
6778
1325
146
6106
1352
153
50
45.5
8756
1362
135
7988
1394
142
7246
1425
150
6531
1457
157
60 Hz Performance
Return gas temp. 65F, 5F sub cooling