Performance Data Sheet

Sept. 18, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA4488ANAD*
BoM: 2G749-** R-12 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
H
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJA4488ANADC
20.0 14.3 12.1 12.0
5/8” S
3/8” S
7.2 lbs
230 22
64
AJA4488ANADP
5/8” S
3/8” S
7.2 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 90°F 100°F 110°F
°F PSIG BTUH Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
20
21.0
5800
1020
114
5450
1050
121
5100
1070
129
25
24.6
6380
1085
116
6000
1120
123
5650
1145
131
30
28.5
6950
1150
117
6550
1190
125
6200
1220
132
40 37.0 8200 1290 121 7800 1330 129 7400 1380 137
45
41.7
8800
1360
123
8400
1400
131
8000
1460
139
50
46.7
9500
1430
125
9050
1480
133
8600
1540
142
60 Hz Performance
Return gas temp. 65°F, 5°F sub cooling