Performance Data Sheet

Sept. 18, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA7455YAAD*
BoM: 2G742-** R-134a 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
W
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJA7455YAADC
20.0 14.3 12.1 11.6
5/8” S
3/8” S
6.6 lbs
230 26
64
AJA7455YAADP
5/8” S
3/8” S
6.6 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 80°F 90°F 100°F 110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10 1.9 2755 640 96 2438 634 105 2035 609 113 1651 574 121
-5
4.2
3286
709
99
2913
697
108
2470
677
116
2063
654
124
0
6.5
3831
781
102
3405
769
111
2926
754
119
2492
738
127
5 9.1 4388 858 106 3914 850 115 3401 837 122 2938 825 130
10
11.9
4958
939
110
4439
938
118
3896
929
125
3401
916
133
15
15.0
5542
1024
113
4981
1035
122
4412
1028
129
3882
1010
137
20 18.4 6138 1114 117 5540 1140 125 4947 1135 133 4380 1108 141
25
22.1
6747
1208
121
6116
1253
129
5502
1250
137
---
---
---
30
26.1
7370
1305
125
6709
1375
133
6077
1372
141
---
---
---
35 30.4 8005 1408 129 7318 1504 137 --- --- --- --- --- ---
60 Hz Performance
Return gas temp. 40°F, 5°F sub cooling

Summary of content (3 pages)