Performance Data Sheet

Sept. 18, 2014
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AJA7465AAAD*
BoM: 2G744-** R-12 3/4 HP
Large Capacity Pump Down Unit
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
H
CH
Suction
Liquid
90 °F 90%
SCFM
Oz.
Lbs.
AJA7465AAADC
20.0 14.3 12.1 11.6
5/8” S
3/8” S
7.2 lbs
230 22
64
AJA7465AAADP
5/8” S
3/8” S
7.2 lbs
64
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T, 90°F 100°F 110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
0
9.2
4260
870
121
4020
890
124
3780
910
127
10 14.6 5355 1000 125 5110 1020 128 4830 1040 132
15
17.7
5960
1085
127
5690
1110
130
5450
1130
133
20
21.0
6560
1180
129
6300
1210
133
6080
1230
136
25 24.6 7200 1280 132 6880 1315 135 6600 1350 138
30
28.4
7650
1400
135
7510
1435
138
7190
1470
142
60 Hz Performance
Return gas temp. 40°F, 5°F sub cooling