Performance Data Sheet

January 23, 2013
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AKA9435ENAD*
BoM: 2G304-** R-22 1/2 HP
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
H
CH
Suction
Liquid
90 F 90%
SCFM
Oz.
Lbs.
AKA9435ENADA
15.0
11.2
10.1
3/8” S
1/4” S
N/A
185
15
52
AKA9435ENADG
3/8” S
3/8” S
2.5 lbs
54
AKA9435ENADH
3/8” S
3/8” S
N/A
52
AKA9435ENADK
3/8” S
1/4” S
52
AKA9435ENADC
3/8” S
3/8” S
2.5 lbs
54
AKA9435ENADS
3/8” S
3/8” S
N/A
52
AKA9435ENADJ
3/8” S
3/8” S
2.5 lbs
54
AKA9435ENADP
3/8” S
3/8” S
2.5 lbs
54
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T,
80°F
90°F
100°F
110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
16.5
1677
396
91
1600
389
100
1106
415
105
853
415
107
-5
20.0
1997
426
93
1848
423
102
1405
441
108
1141
442
111
0
24.0
2340
457
95
2124
458
104
1721
468
110
1445
472
115
5
28.2
2707
489
98
2428
493
106
2056
498
113
1763
504
119
10
32.8
3096
522
101
2760
529
109
2408
530
116
2096
538
122
15
37.7
3509
555
103
3121
566
112
2778
564
119
2445
575
126
20
43.0
3944
589
106
3510
604
114
3166
600
122
2809
613
130
25
48.8
4403
624
109
3928
642
117
3572
639
125
3188
655
133
30
54.8
4885
659
112
4373
680
120
3995
680
128
3582
698
137
35
61.5
5390
695
116
4847
720
124
4437
723
131
3991
744
140
40
68.5
5918
732
119
5349
760
127
4896
769
135
---
---
---
45
76.0
6469
769
122
5879
800
130
5373
816
138
---
---
---
60 Hz Performance
Return gas temp. 40F, 5F sub cooling

Summary of content (3 pages)