Performance Data Sheet

January 25, 2013
Revision: REL
Celseon® Air Cooled Condensing Unit
Model: AKA9470ENAD*
BoM: 2G719-** R-22 3/4 HP
Model
Dimensions, inches
Line Connection*
Pumpdown
Air
Oil Ch
Gr. Wt.
L
H
CH
Suction
Liquid
90 F 90%
SCFM
Oz.
Lbs.
AKA9470ENADA
24.0
13.4
10.2
3/8” S
3/8” S
N/A
270
15
66
AKA9470ENADG
3/8” S
3/8” S
7.1 lbs
67
AKA9470ENADH
3/8” S
3/8” S
N/A
66
AKA9470ENADK
3/8” S
3/8” S
66
AKA9470ENADC
3/8” S
3/8” S
7.1 lbs
67
AKA9470ENADS
3/8” S
3/8” S
N/A
66
AKA9470ENADJ
3/8” S
3/8” S
7.1 lbs
68
AKA9470ENADP
3/8” S
3/8” S
7.1 lbs
68
* F = Flare, S = Solder, RF or RS = Rotolock with Flare or Solder Connections, C = Compression Fitting
Factory charge: 20 PSIG Nitrogen MUST BE EVACUATED
Ambient Temperatures
Evaporator T,
90°F
100°F
110°F
°F
PSIG
BTUH
Watts
Cond T
BTUH
Watts
Cond T
BTUH
Watts
Cond T
-10
16.5
3200
830
100
2800
830
108
---
---
---
-5
20.0
3800
870
100
3300
800
108
3000
890
116
0
24.0
4300
920
101
3800
930
110
3500
940
117
5
28.2
5000
970
103
4500
990
111
4000
1000
119
10
32.8
5600
1020
105
5100
1040
113
4600
1060
121
15
37.7
6300
1070
108
5700
1090
116
5300
1120
123
20
43.0
7000
1130
110
6400
1150
119
5900
1180
126
25
48.8
7800
1180
113
7100
1210
120
6500
1240
128
30
54.8
8500
1240
116
7800
1270
123
7200
1310
131
35
61.5
9300
1290
119
8600
1330
126
7900
1390
133
40
68.5
10100
1360
121
9300
1400
128
8600
1450
136
45
76.0
10900
1430
124
10100
1480
131
9300
1530
138
60 Hz Performance
Return gas temp. 40F, 5F sub cooling