Performance Data Sheet

L:\~ Andreea temp\~ DATA SHEETS\Outdoor Datasheets\WORD_Datasheets\High Temp Applications\AVA4540EXNHN_rev1.doc 06/01/2012
Unit BOM 32L3127-2E
Fan Motor 810F050C20 Defrost Clock
(
Tn o
p
tion
)
84110
Unit MODEL AVA4540EXNHN
Fan Motor Qt
y
2 Defrost Heaters Contactor 91014
Fan Motor RLA 0.7
Refrigeration RANGE (20°F to 55°F) Fan Blade 51568 Rec. Heater (R option) LHR-222
Design Pressure Low 150 Fan Guard 70831 Solenoid Valve (loose) KSVC-264
Design Pressure High 450 Shroud 70648-2
Volts - HZ - Ph 208-230V ~ 60HZ Disconnect (D option) LDSG-613
Voltage Range 187 - 253 High Pressure switch 84095-1L
Min. Circuit Ampacity 28.05 Low Pressure Control 84026-D
Max. Fuse Size 50 Dual Pressure Conrol
Compressor MODEL AVA5542EXN Condenser 50858
Compressor BOM AV144ET-001-A2 Head Master Valve 70083-1 Wiring with A option WD21-2AT2
Compressor LRA 108 Check Valve 56626
Compressor RLA 21.15 Process Valve
Liquid Valve
OverLoad INTERNAL Suction Valve 31529-1
32xYYYY- 2ERA(F)TnDS
Relay 820ARR3H46 E Enclosure
Run Capacitor 85PR440F28 Receiver 51099-2L R Receiver Heater
Run Capacitor Rating 40 MFD, 440 V Receiver Qty 1 A Adjustable fan control
Start Capacitor 85PS330D16 Accumulator TK00042000 F Fixed fan Control
Start Capacitor Rating 130-156 MFD, 330 V Liquid Filter 52000-084D T1 Defrost timer option
Contactor 91014 Sight Glass SG-08DF T2 Defrost timer & Defrost Heaters Contactor
Suction Filter 70822-5S D Disconnect
Unit Drawing DGU1920-L101 S Solenoid liquid Valve (supplied loose)
Wiring Diagram WD21-2XT2 CrankCase Heater 90699
BOM INDEX DESCRIPTION
Parts/Specifications
STANDARD OPTIONAL
WD21-2XT2
NOV 06, 2009
B
REVISION
POTENTIAL RELAY
see note B
5
2
COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD
PROTECTOR. ALLOW TIME FOR RESET.
USE COPPER CONDUCTORS ONLY.
(EMPLOYER DES CONDUCTEUERS DE CUIVER
SEULEMENT.)
DEFROST
HEATERS
CONTACTOR COIL
FAN 2
L1
CRANK CASE
HEATER
COMPRESSOR
TERMINAL
C
S
R
GRD
L1 T1
RED
YELLOW
BLACK
COMPRESSOR
CONTACTOR
T1
L1
T2
L2
COMPRESSOR CONTACTOR
NC AUXILIARY SWITCH
RECEIVER
HEATER
L3
L2
T3
T2
COMPRESSOR
CONTACTOR COIL
see note A
TERMINAL
BOARD
P1
HP LP
RED
BLACK
YELLOW
L1
T1T3
L3
DEFROST
HEATERS
CONTACTOR
START
CAPACITOR
WITH BLEEDER
RESISTOR
T2
L2
T3
L3
4
6
1
L2 L3 T3T1 F1 F2
FIELD INSTALLED
SOLENOID & THERMOSTAT
ROOM
THERMOSTAT
1
3
Solenoid
Valve
DEFROST CONTROL
RANCO 8145-xx
PRECISION 6145-xx
N
2
4
X
IMPORTANT:
FAN 1
GENERAL NOTES:
A. CONTACTOR COIL CIRCUIT IS FACTORY CONNECTED TO 230 V SOURCE IN
PANEL AS SHOWN
B. WITH ANY T.P.Co. APPROVED START RELAY USED, CONNECT LEADS TO
SAME NUMBERED TERMINALS REGARDLESS OF LOCATION
C. COMPRESSOR EQUIPPED WITH AN INTERNAL OVERLOAD PROTECTOR.
ALLOW TIME FOR RESET.
CONDENSING UNIT WIRING, 230V 60Hz 1 Ph,
NO fan controls,
T1 & T2 defrost options
RUN
CAPACITOR
FACTORY COMPONENTS
OPTIONAL FIELD COMPONENTS
OPTIONAL FACTORY COMPONENTS
HP
LP
LOW PRESSURE CONTROL
HIGH PRESSURE SWITCH
FIELD WIRING NOTES
1. ALL FIELD WIRING MUST BE DONE IN COMPLIANCE WITH ALL
APPLICABLE LOCAL AND NATIONAL CODES.
2. CONNECT INCOMING POWER LEADS FROM POWER SUPPLY
TO L1, AND L3 IN COMPRESSOR CONTACTOR (L1 AND L2 IF TWO POLE
CONTACTOR) OR TO L1 AND L3 IN DISCONNECT SWITCH (IF PROVIDED).
USE COOPER CONDUCTORS ONLY. (EMPLOYER DES CONDUCTEURS
DE CUIVER SEULEMENT.) PROVIDE EQUIPMENT GROUNDING
CONDUCTOR. USE 75°C (MIN.) WIRING
3. PLACE JUMPER ACCROSS P1 AND L1 IN TERMINAL BOARD IF NO
OTHER CONTROLLING DEVICE IS INSTALLED.
4. DEFROST HEATERS LOADS SHOULD NOT BE HIGHER THEN THE
MAXIMUM HEATERS LOAD INDICATED ON THE UNIT LABEL.
NOTES
HEATER
THERMOSTAT
POWER SUPPLY
230-60-1
AVA4540EXNHN
TPC___rev 1 January 6, 2012