Install Instructions

1 of 4 © 2007 D 073 - 05/07
- Data Brochure
Slab Sensor 073
D 073
05/07
Installation - Slab Sensor 073
Slab Sensor 073
The tekmar Slab Sensor 073 has a PVC
plastic sleeve which is designed for use in
soils or concrete. The 073 is supplied with
40’ (12 m) of 2 conductor cable.
STEP ONE
INSTALLING THE SENSOR
NOTE: Proper placement of this sensor is critical
for correct operation of the control.
This sensor is designed to be embedded in the
slab material. However, it is recommended that
the sensor be installed in a plastic or metal conduit
embedded in the slab. If there is ever a sensor
failure, this allows the sensor to be removed and
replaced. The sensor should be placed 1” (25 mm)
below the slab surface and 1/2 way between the
pipes or electric cables.
STEP TWO
WIRING AND TESTING THE SENSOR
Caution: Do not run sensor wires parallel to telephone or power cables. If the sensor wires
are located in an area with strong sources of electromagnetic interference, shielded cable
or twisted pair should be used or the wires can be run in a grounded metal conduit. The
ground wire should be connected to the common sensor terminal on the control and not
to earth ground.
The Slab Sensor 073 is supplied with 40’ (12 m) of cable. If a longer length is required, 18
AWG wire can be spliced onto the two wires from the sensor. The splices should be properly
soldered and protected in an accessible, waterproof junction box. Follow the sensor testing
instructions given in this brochure and then connect the wires to the control.
Slab Sensor 073 placed 1/2 way between the
pipes or cables inside the conduit
1” (25 mm)