Installation - Universal Sensor 078
The tekmar Universal Sensors have a brass sleeve for fast response and a wide operating 
range. These sensors can be used in a multitude of applications. The 078 is supplied with 
15 ft (4572 mm) of two conductor wire.
STEP ONE
MOUNTING THE SENSOR
NOTE: These sensors are designed to mount on a pipe or in a temperature immersion well.
The Universal Sensor can be strapped directly to the 
pipe using the cable tie provided. Insulation should 
be placed around the sensor to reduce the effect of 
air currents on the sensor measurement.
The Universal Sensor should be placed downstream 
of a pump or after an elbow or similar fitting. This is 
especially important if large diameter pipes are used 
as the thermal stratification within the pipe can result 
in erroneous sensor readings. Proper sensor location 
requires that the fluid is thoroughly mixed within the 
pipe before it reaches the sensor.